COMMERCIAL INSPECTION - 1221 FRANKLIN ST - 2-8-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price j
$70.00
$10.00
CUSTOMER #
21820
BILLING DATE
02/14/2024
DUE DATE
03/20/2024
INVOICE #
2024-00000278
CHARGES
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
MICHOACANA,,1221 FRANKLIN ST, BLD6 1221 FRANICLIN ST, WATERLOO IA 50703
DETAILS
Inspection Date: 02/08/2024 Inspection Type: Annual Inspection (1Yr) ! Inspection Number: 10051 ! Shift: N/A ! Station: N/A
Unit: N/A j Lead Inspector: JEFF SIEBEL Other Inspectors: N/A Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 35 I Violations: 4 I N/A Codes: 34
STATUS CODE DESCRIPTION
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
FAI L
606.3.3 - Cleaning.
Location: Office
Original Comment: remove portable electric heater or provide documentation of
listing for use in commercial building and proper clearances. Heater was running
in unoccupied office.
Hoods, grease -removal devices, fans, ducts and other appurtenances shall be
cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3.
Location: Kitchen hood cleaning
Original Comment: AKA hood cleaning report dated 1/2/24 lists deficiencies
(hinge kit). Provide corrections. Contractor must upload corrections online.
Printed on 02/09/2024 @ 10:12
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: Hood fire suppression (Ansul System)
Original Comment: Provide current semi-annual kitchen hood fire suppression
inspection report with all discrepancies corrected. Currently 57 days past due.
Contractor must upload online to the compliance engine.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1 Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERAL NOTES
Location: kitchen by exhaust hood
Original Comment: replace missing ceiling tile.
Printed on 02/09/2024 @ 10:12
Page 2 of 3
JEFF SIEBEL - 02/09/2024 @ 10:08 annual inspection $80