COMMERCIAL INSPECTION - 1215 FRANKLIN ST - 2-8-24
L Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
14785
02/14/2024
03/20/2024
2024-00000277
CHARGES
Less Prepayment
Total Due —>
City of Waterloo
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
MICHOACANA MEAT MARKET, 121S FRANKLIN ST, BLDG 1215 FRANKLIN ST, WATERLOO IA
50703
DETAILS
Inspection Date: 02/08/2024 ; Inspection Type: Annual Inspection (1Yr) j Inspection Number: 10052 I Shift: N/A ; Station: N/A j
Unit: N/A ': Lead Inspector: JEFF SIEBEL Other Inspectors: N/A Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 ( Passed Codes: 27 I Violations: 4 I N/A Codes: 43
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: Mechanical room grocery side
Original Comment: Obtain permit and inspections for AC unit installed.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Above front door
Original Comment: Repair exit/egress light
Printed on 02/09/2024 @ 10:31
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
FAI L
Location: Ceiling above AC unit in mechanical room
Original Comment: Obtain permit and inspection to repair fire rated ceiling
around AC line set and cut-off PVC.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Fire door to restaurant
Original Comment: Repair fire door. Door must completely self -close and latch.
Remove obstructions.
Printed on 02/09/2024 @ 10:31
Page 2 of 3
STATUS
GENERAL NOTES
CODE DESCRIPTION
JEFF SIEBEL - 02/09/2024 @ 10:31 annual inspection $80
REINSPECTION DATE
03/08/2024
CONTACT SIGNATURE
Blanca Garcia
Signed on: 02/09/2024 @ 10:28
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/09/2024 @ 10:28
QUESTIONS ABOUT TOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/09/2024 @ 10:31
Page 3of3