COMMERCIAL INSPECTION - 2450 CROSSROADS BLVD - 2-8-24
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 50,000
OCCUPANCY FEE
Total Price ]
$225.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
13032
02/14/2024
03/20/2024
2024-00000275
$235.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$235.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
MARCUS THEATERS, 2450 CROSSROADS BLVD, BLDG 2450 CROSSROADS BLVD, WATERLOO IA
50702
DETAILS
Inspection Date: 02/08/2024 1 Inspection Type: Annual Inspection (1Yr) 1 Inspection Number: 9970 I Shift: N/A Station: N/A 1
Unit: N/A j Lead Inspector: JEFF SIEBEL 1 Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 1 Passed Codes: 44 1 Violations: 9 1 N/A Codes: 22
STATUS CODE DESCRIPTION
FAIL
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: outside exit by theater 3.
Original Comment: Repair exit door. Must unlatch and swing to full open with less
than 15# force.
Printed on 02/08/2024 @ 09:11
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAI L
FAIL
Location: Not Provided
Original Comment: Emergency light testing by Brandon Kline completed 1/25/24
lists deficiencies. Provide documentation of corrections with signature and date
or invoice.
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
Location: Not Provided
Original Comment: Fire alarm panel displays trouble. Provide corrections
5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Location: Not Provided
Original Comment: Fire Sprinkler inspection from 12/28/23 lists discrepancies.
Contractor must upload corrections online to the compliance engine.
Printed on 02/08/2024 @ 09:11
Page 2of5
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Theater 1
Original Comment: Replace missing ceiling tile.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Theater 9
Original Comment: Replace theater 9
Printed on 02/08/2024 @ 09:11
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Storage room by Men's restroom and theater 1
Original Comment: replace missing ceiling tile.
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: Entire building
Original Comment: fire extinguishers due now
Printed on 02/08/2024 @ 09:11
Page 4of5
STATUS CODE DESCRIPTION
FAIL Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
Location: Not Provided
Original Comment: Provide current fire alarm inspection report with all
discrepancies corrected. Currently past due. Contractor must upload online to
the compliance engine.
GENERAL NOTES
JEFF SIEBEL - 02/08/2024 @ 09:07 annual inspection $235
REINSPECTION DATE
02/28/2024
CONTACT SIGNATURE
Brandon Kline manager 2023
Signed on: 02/08/2024 @ 09:08
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/08/2024 @ 09:08