COMMERCIAL INSPECTION - 1615 BISHOP AVE - 2-9-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20738
02/14/2024
03/20/2024
2024-00000273
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
B & B EAST, 161S BISHOP AVE, BLDG 1615 BISHOP AVE, WATERLOO /A S0707
DETAILS
Inspection Date: 02/09/2024 j Inspection Type: Annual Inspection (1Yr) I Inspection Number: 10471 ! Shift: N/A ; Station: N/A j
Unit: N/A I Lead Inspector: JEFF SIEBEL j Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 33 I Violations: 5 I N/A Codes: 37
STATUS CODE DESCRIPTION
FAIL 305.1 - Clearance from Clearance between ignition sources, such as luminaires, heaters, flame -
ignition sources. producing devices and combustible materials, shall be maintained in an
approved manner.
Location: room behind office. Water heater
Original Comment: remove obstructions . Maintain a minimum of 36" clearance
at all times.
Printed on 02/09/2024 @ 10:06
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL
FAIL
5303.5.3 - Securing
compressed gas containers,
cylinders and tanks.
603.4 - Working space and
clearancesclearance.
Compressed gas containers, cylinders and tanks shall be secured to prevent
falling caused by contact, vibration or seismic activity. Securing of compressed
gas containers, cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object with one or more
restraints. 2.Securing containers, cylinders and tanks on a cart or other mobile
device designed for the movement of compressed gas containers, cylinders or
tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container
filling or servicing facilities or in sellers' warehouses not open to the public.
Nesting shall be allowed provided that the nested containers, cylinders or tanks,
if dislodged, do not obstruct the required means of egress. 4.Securing of
compressed gas containers, cylinders and tanks to or within a rack, framework,
cabinet or similar assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of examination, filling, transport or
servicing.
Location: behind office
Original Comment: secure all compressed gas cylinders with CHAIN
A working space of not Working space around electrical equipment shall be
provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: Back room behind cooler
Original Comment: Remove obstructions to electric panel. maintain a minimum
of 36" clearance at all times.
Printed on 02/09/2024 @ 10:06
Page 2 of 4
STATUS
FAI L
FAI L
CODE
603.6 - Extension cords.
DESCRIPTION
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: front glass pipe and ball display cabinet
Original Comment: Remove extension cord from ceiling to display case. Install
permanent outlet with permits and inspections.
904.14.1 - Protection from Cooktops and ranges shall be protected in accordance with Section 904.14.1.1 or
fire. 904.14.1.2.
Location: kitchen
Original Comment: Remove electric griddle or relocate under the exhaust hood
with fire suppression coverage. Hood must overhang appliance by a minimum of
6"
Printed on 02/09/2024 @ 10:06
Page 3 of 4
STATUS
CODE
REINSPECTION DATE
03/07/2024
CONTACT SIGNATURE
Joyce
Signed on: 02/09/2024 @ 09:35
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/09/2024 @ 09:36