COMMERCIAL INSPECTION - 2034 LA PORTE RD - 12-6-23
L Description
FOR BILLING INQUIRY: (319)291-4323
REINSPECTION 1
Total Price ]
$100.00
CUSTOMER #
12855
BILLING DATE
01/02/2024
DUE DATE
02/05/2024
INVOICE #
2024-00000228
CHARGES
Less Prepayment
Total Due —�
City of Waterloo
$100.00
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HAMPTON INN & SUITES, 2034 LA PORTE RD, BLDG 2034 LA PORTE RD, WATERLOO IA 50702
DETAILS
Inspection Date: 12/06/2023 I Inspection Type: Annual Inspection (1Yr) Inspection Number: 11521 Shift: N/A ; Station: N/A j
Unit: N/A j Lead Inspector: JEFF SIEBEL Other Inspectors: N/A ( Fee: $100.00
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the International
code. Building Code , and any alterations, additions, changes in use or changes in
structures required by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Inspector: JEFF SIEBEL - Comments: Obtain permit and final inspection for new fire
door for pool chemical room
Location: Fire Door Pool Chemical Room
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the International
code. Building Code , and any alterations, additions, changes in use or changes in
structures required by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Inspector: JEFF SIEBEL - Comments: Obtain permit and inspections for repair of fire
rated ceiling.
Location: Hall outside restrooms on first floor
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the International
code. Building Code , and any alterations, additions, changes in use or changes in
structures required by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Inspector: JEFF SIEBEL - Comments: Obtain final inspection for sheetrock repairs in
fire rated walls and ceiling.
Location: Maids closet and 1st floor ceiling
Printed on 12/07/2023 @ 10:13
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the International
code. Building Code , and any alterations, additions, changes in use or changes in
structures required by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Inspector: JEFF SIEBEL - Comments: Obtain permits and inspections for new water
heater installations.
Location: Water heaters room on first floor
FAIL 2015 IFC- Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation (no
and maintenance troubles, supervisory, or alarms)?
Inspector: JEFF SIEBEL - Comments: Smoke Detector must be secured to ceiling.
Location: Room 409
FAIL 2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation (no
and maintenance troubles, supervisory, or alarms)?
Inspector: JEFF SIEBEL - Comments: secure smoke detector to ceiling.
Location: room 301
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less, and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts. The minimum required working space shall be not less than 30 inches (762 mm)
in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the minimum working space shall be
not less than the width of the equipment. Storage of materials shall not be located
within the designated working space. Exceptions: 1. Where other dimensions are
required or allowed by NFPA 70. 2. Access openings into attics or under -floor areas
that provide a minimum clear opening of 22 inches (559 mm) by 30 inches (762 mm).
Inspector: JEFF SIEBEL - Comments: Remove obstructions to electrical panel. Maintain
a minimum of 36" clearance at all times.
Location: maid closet by room 400
Printed on 12/07/2023 @ 10:13
Page 2of5
STATUS CODE
DESCRIPTION
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector: JEFF SIEBEL - Comments: Provide documentation of dryer vent cleaning to
the outside of the building with signature and date. Remove excess lint from bottom
motors of commercial dryers. repair pipe on guest dryer.
Location: Commercial Dryers and guest dryers
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained. The
materials and systems shall be securely attached to or bonded to the adjacent
construction, without openings visible through the construction. 1.Joints in or
between fire -resistance -rated walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall. 4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall. 5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall. 6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall. 7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed. Where the system design number is known, the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector: JEFF SIEBEL - Comments: Repair sheetrock ceiling above dropped
ceiling(fire rated) with permit and inspections.
Location: Outside restrooms in hall ceiling
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch automatically.
Inspector: JEFF SIEBEL - Comments: Fire Door must completely self close and latch
Location: 4th floor elevator fire door
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch automatically.
Inspector: JEFF SIEBEL - Comments: Door must completely self -close and latch
Location: room 407
Printed on 12/07/2023 @ 10:13
Page 3of5
STATUS CODE DESCRIPTION
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch automatically.
Inspector: JEFF SIEBEL - Comments: Fire door must completely self close and latch
Location: Door between condiment room and kitchen
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch automatically.
Inspector: JEFF SIEBEL - Comments: Fire door must completely self -close and latch.
Location: room 129
GENERAL NOTES
JEFF SIEBEL - 12/07/2023 @ 10:09
Items rolled over from last years inspection: Fire door permits and inspections still
required and final inspection on sheetrock and doors required. Re -inspection fee of
$200 will resume if not completed.
JEFF SIEBEL -12/07/2023 @ 10:08 Annual inspection fee $100
REINSPECTION DATE
12/28/2023
CONTACT SIGNATURE
Mitch Goodrich - Maintenance
Signed on: 12/07/2023 @ 10:10
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 12/07/2023 @ 10:10
Printed on 12/07/2023 @ 10:13
Page 4 of 5