COMMERCIAL INSPECTION - 4051 UNIVERSITY AVE - 6-23-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
24739
BILLING DATE
07/09/2025
DUE DATE
08/12/2025
INVOICE #
2026-00000002
CHARGES
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Repo
hurch - 4051 University AVE, B DG 4051 University Ave, Waterloo IA 50701
(INSPECTION TAILS
Inspection Date,
\ 06123/2025 f
` i Insp for
Brad Baldwin
Other Inspectors
NIA
Inspection Type
Annual Inspection (1Yr) ; REINSPECTION
Shift
NIA
425 E. 3rd Street
Inspection Number
7418-R1
Station Unit
NIA N/A
SUMMARY OF INSPECTION
0
Passed codes
NEXT STEPS
Q 18
Failed codes
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 3192914319
Brad Baldwin - 0612412Q25 @ 07:43
$100 re -inspection fee, failure to show for scheduled inspection on 6/23/25 at 1:30pm.
Reinspection Date
07/16/2025
Brad- Bat - 051 2025 @ 15:09
-Re-inspection dates are automatically generated 30 days out from the initial inspection. If all corrections are made before the 30 days, you can call to set
up an earlier re -inspection. Normal operating hours for inspections & re -inspections are Monday a€" Friday, 9:00 a.m. a€" 4:00 p.m. *****Re inspection
fees may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re -inspections. -
Brad Baldwin - 05/13/2025 @ 15:09
-Property Safety Inspector a€" brad.baldwin@waterloo-ia.org a€" Work: 319-291-4319
Brad Baldwin - 05113/2025 @ 15:09
$80 Annual inspection fee
SIGNATURES
Contact signature Inspector signature
John Latdrik (Pastor)
CHECKLISTS
No signature
Report completed post inspection
Date: Brad Baldwin 0612412025
GENERATED ON 6/24/25, 8:13 AM 1 OF 6
Reinspection
Status Code
Fail
Fait
cpc
Fail
Fail
0
Fail
Fail
Fail
/Fail
1004.9
Every room or space that is an assembly occupancy shall
have the occupant load of the room or space posted in a
conspicuous place, near the main exit or exit access doorway
from the room or space, for the intended configurations.
Posted signs shall be of an approved legible permanent
design and shall be maintained by the owner or the
owners€" s authorized agent.
102.3
A change of occupancy shall not be made unless the use or
occupancy is made to comply with the requirements of this
code and the International Existing Building Code .
Exception: Where approved by the fire code official, a change
of occupancy shall be permitted without complying with the
requirements of this code and the International Existing
Building Code , provided that the new or proposed use or
occupancy is less hazardous, based on life and fire risk, than
the existing use or occupancy.
102.4
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
1203.2.15
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
5.2.1
Sprinklers shall be inspected at least annually by licensed
contractor
5.2.1.1.5
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Desci
p
on
Location: Occupant load posting
Comments: Occupant load shall be reviewed by licensed designed
professional. Report shall be sent to fire inspector.
Location: Change of occupancy
Comments: Change of occupancy must be reviewed by a licensed
design professional. Report by professional shall be submitted to be
reviewed by City Building Official.
Location: Walls constructed in SE corner
Comments: Walls constructed without building permit. Obtain
architect to submit plans for review of by City Building Official
Location: Walls constructed outside women's bathroom
Comments: Walls constructed without building permit. Obtain
architect to submit plans for review of by City Building Official
Location: Exit sign near alter
Comments: Exit light above front entrance doors failed testing, repair
or replace.
Location: Front entrance exit light
Comments: Exit light above front entrance doors failed testing, repair
or replace.
Location: Sprinkler system
Comments: Complete sprinkler system testing and inspection,
currently past due 578 days as of 5113/25. Contractor must upload
report online to Compliance Engine
Location: Northwest corner sprinkler escutcheon
Comments: Install sprinkler escutcheon properly
GENERATED ON 6/24/25, 8:13 AM 2 OF 6
Fail
x
Fail
x
Fail
Fail
509.2
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
603.5
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5.2
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.5.3
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Sprinkler riser room
Comments: Remove all storage.
Location: All multiplug adapters and cords
Comments: Multiplug adapters and multiplug cords shall be
removed.
Location: All power strips
Comments: All power strips shall be plugged directly to wall
receptacle.
Location: Near posts in center of building and near front wall.
Comments: Cords running through ceiling grids shall be permanently
removed.
Location: Several extension cords noted
Comments: Remove all extension cords.
GENERATED ON 6/24/25, 8:13 AM 3 OF 6
807.2
In Groups A, B, E, 1, M and R-1 and in dormitories in Group R-
2, curtains, draperies, fabric hangings and other similar
combustible decorative materials suspended from walls or
ceilings shall comply with Section 807.3 and shall not exceed
10 percent of the specific wall or ceiling area to which such
materials are attached. Fixed or movable walls and partitions,
paneling, wall pads and crash pads applied structurally or for
decoration, acoustical correction, surface insulation or other
purposes shall be considered to be interior finish, shall
comply with Section 803 and shall not be considered
decorative materials or furnishings. Exceptions: 1.1n
auditoriums in Group A, the permissible amount of curtains,
draperies, fabric hangings and similar combustible decorative
material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1, and where the
material is installed in accordance with Section 803.15 of the
International Building Code. 2.In Group R-2 dormitories,
within sleeping units and dwelling units, the permissible
amount of curtains, draperies, fabric hangings and similar
decorative materials suspended from walls or ceilings shall
not exceed 50 percent of the aggregate wall areas where the
building is equipped throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.
3.In Group B and M occupancies, the amount of combustible
fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 807.3 and
shall not be limited. 4.The 10-percent limit shall not apply to
curtains, draperies, fabric hangings and similar combustible
decorative materials used as window coverings.
Location: Wall coverings near alter
Comments: Verify draperies meet flame spread requirements
GENERATED ON 6/24/25, 8:13 AM
4 OF 6
Fail
Fail
Fail
x
906.1
Portable fire extinguishers shall be installed in all of the
following locations: 1.In new and existing Group A, B, E, F, H,
1, M, R-1, R-2, R-4 and S occupancies. Exceptions: 1.In Group
R-2 occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C. 2.In Group E
occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C. 3. In storage areas of Group
S occupancies where forklift, powered industrial truck or
powered cart operators are the primary occupants, fixed
extinguishers, as specified in NFPA 10, shall not be required
where in accordance with all of the following: 3.1. Use of
vehicle -mounted extinguishers shall be approved by the fire
code official. 3.2. Each vehicle shall be equipped with a 10-
pound, 40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use. 3.3. Not less than
two spare extinguishers of equal or greater rating shall be
available on -site to replace a discharged extinguisher. 3.4.
Vehicle operators shall be trained in the proper operation, use
and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30
feet (9144 mm) distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group 1-
1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed. 4.On each floor of structures under
construction, except Group R-3 occupancies, in accordance
with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but
not limited to laboratories, computer rooms and generator
rooms, where required by the fire code official. Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.
Chapter 14
Fire alarm system tested at least annually by licensed
contractor
Table 8.1.1.2
Fire pump being tested (run)? Weekly for diesel/monthly for
electric.
Additional Codes
sehz:s Code
Fail
X1
102.4
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Location: Fire extinguishers
Comments: Install fire extinguishers where required by code. Copy of
receipt shall be kept for purchase of fire extinguishers
Location: Fire alarm system
Comments: Complete fire alarm system testing and inspection,
currently past due 388 days as of 5/13/25. Contractor must upload
report online to Compliance Engine
Location: Sprinkler system testing & inspection
Comments: Complete sprinkler system testing and inspection,
currently past due 578 days as of 5/13/25. Contractor must upload
report online to Compliance Engine.
Description
Location: Wall constructed separating church from south area of
building
Comments: Wall constructed without building permit. Obtain
architect to submit plans for review by of by City Building Official.