COMMERCIAL INSPECTION - 1104 WASHINGTON ST - 6-25-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
CUSTOMER #
14228
Total Price
$70.00
$10.00
BILLING DATE
07/09/2025
DUE DATE
08/12/2025
INVOICE #
2026-00000016
CHARGES
Less Prepayment
Total Due —�
City of Waterloo
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
Tate fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report\
Kwik Stop 3 - 1104 Washington St, BLDG 1104 Washington St - STE A, Waterloo IA
50702
INSPECTION -DETAILS" —
inspection Date
06/25/2025
adInspector
Br.: n
Other Inspectors
NIA
Inspection Type
glnnual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
14216
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 29
Passed codes
NEXT STEPS
CD 11
Failed codes
0 34
NIA codes
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Brad Baldwin - 0612612025 @ 07:50
$80 annual inspection fee
Brad Ba wiff=0572V2025 @ 07:50
ACC Commercial Fire Inspector a€" brad.baldwin@waterloo-ia.org a€" Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
07/17/2025
Brad Baldwin - 06/2612025 @ 07:50
a€rC Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
Brad Baldwin - 06/2612025 @ 07:50
ACC If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday a€" Friday, 9:00 a.m. a€" 4:00 p.m. ****'Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Mohammad ILYAS Date: _ Brad Baldwin 06/26/2025
CHECKLISTS
GENERATED ON 6/26/25, 8A8 AM
1 OF 9
Means of Egress
Status Code
Fail
1032.2
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Back storage area exit
Comments: Remove obstructions to clear path of egress. Second exit
in storage area is not required per square footage . Removal of exit
sign would be approved per City Building Official, removal would
require wires properly capped in box with cover.
GENERATED ON 6/26/25, 8:48 AM
2 OF 9
General Housekeeping
Status Code
Fail
0
315.3.1
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Location: Back storage room
Comments: Remove storage within 24" from ceiling. Storage shall be
neatly stacked to avoid tip over hazard.
GENERATED ON 6/26/25, 8:48 AM
3 OF 9
Fail
315.4.1
Where buildings are protected by an automatic sprinkler
system, the outdoor storage, display and handling of
combustible materials under eaves, canopies or other
projections or overhangs are prohibited except where
automatic sprinklers are installed under such eaves, canopies
or other projections or overhangs.
Location: Front entrance
Comments: Remove firewood and all combustible material from
under eave of building.
GENERATED ON 6/26/25, 8:48 AM 4 OF 9
Electrical Safety
Status :`odor
Fail
Fail
x
603.2
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: "Fish Game" near front of store
Comments: Remove game appliance cord running across floor to
avoid damage to cord.
Location: South exterior near exhaust discharge
Comments: Repair or replace damaged wiring and conduit.
GENERATED ON 6/26/25, 8:48 AM
5 OF 9
Fail
Fail
0
603.2.2
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Alcohol cooler
Comments: Provide moisture proof cover for cooler light fixture
Location: Back storage near electric panel
Comments: Remove obstructions within 36" in front of electric
panels, maintain clearances at all times.
GENERATED ON 6/26/25, 8:48 AM
6 OF 9
Fail 603.5
0 Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fail 603.5.2
0 Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: Near "fish game" at front of store
Comments: Properly hang or support power strip to avoid hanging by
wires. Appliances shall be plugged directly to wall outlets
Location: Under counter near register
Comments: Remove power strips daisy chained, power strips shall
have manual reset and plugged directly to wall outlet.
GENERATED ON 6/26/25, 8:48 AM
7 OF 9
Portable Fire Extingusihers
Status Code
Fail
Fail
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer.€Cr's
installation instructions,
Descr
p
on
Location: All fire extinguishers
Comments: Provide fire extinguishers service, due by June 2025.
Location: Under counter near "Fish game"
Comments: Fire extinguisher shall be properly mounted on wall
bracket no less than 4" from floor, no more in height than 5' from
floor
GENERATED ON 6/26/25, 8:48 AM 8 OF 9