COMMERCIAL INSPECTION - 2034 LA PORTE RD - 6-23-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 3
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
07/09/2025
08/12/2025
2026-00000009
$200.00
Less Prepayment
Total Due — >
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report_
ampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
13671-R6
SUMMARY OF INSPECTION
0 0 0 3
Passed codes Resolved violations
NEXT STEPS
0 15
Failed codes
Please direct questions about your Inspection to:
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org, 3192301224
GE OT1a ES
Brad Baldwin - 06/24/2025 @ 15:14
$200 Re -inspection fee for failure to correct violations on 6/23/25
JE - r5/22/2025 @ 13:49
Provide corrections to avoid re -inspection fees
JEFF SIEBEL - 05/22/2025 @ 13:49
Annual inspection $235
JEFF SIEBEL - 05122/2025 @ 13:49
Provide corrections to avoid re -inspection fees.
JEFF SIEBEL - 05/22/2025 @ 13:49
Re -inspection fee $100
JEFF SIEBEL - 05/22/2025 @ 13:49
Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for completion of fire door certifications.
JEFF SIEBEL - 05/22/2025 @ 13:49
Re -inspection fee $150
JEFF SIEBEL - 05/22/2025 @ 13:49
Called Mitch on 4/17/25 and he stated no improvement.
JEFF SIEBEL - 05122/2025 @ 13:49
Re -inspection fee $200
JEFF SIEBEL - 05/22/2025 @ 13:49
annual inspection $200
Reinspection Date
07/22/2025
GENERATED ON 6/24/25, 3:22 PM 1 OF 8
JEFF SIEBEL - 0512212025 @ 13:49
We are recommending denial of alcohol license to the City Council because of lack of progress on required certification of guest room fire doors that
were altered during construction.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cayenne Adams - Manager
CHECKLISTS
Date: JEFF SIEBEL 06124/2025
GENERATED ON 6/24/25, 3:22 PM
2 OF 8
Reinspection
Status Code
Fail
Fail
Fail
Fail
0
102.4
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
5.2.1
Sprinklers shall be inspected at least annually by licensed
contractor
5.2.1.1.5
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Descriution
Location: Entire buiding
Comments: Obtain permits and inspections for all work concerning
fire door repair, replacement smoke seals, all hardware replaced.
Please see original attached email with codes concerning information
requiered for fire door hardware. Please contact Building Official
Greg Ahlhelm with questions. 319-291-4319
Location: Annual Standpipe insepction deficiencies
Comments: Provide current annual fire sprinkler stand pipe
inspection report wth all discrepancies corrected. Current report lists
2 discrepancies. Contractor must upload corrections online to the
compliance engine.
Location: Room 300
Comments: replace missing eschutcheon above sink
Location: Entire second floor guest fire doors
Comments: Install approved smoke seal in all fire door openings that
has been removed including stair doors and utility areas. Check all
other floors
GENERATED ON 6/24/25, 3:22 PM 3 OF 8
Fail
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Guest Computer Room
Comments: patch sheetrock ceiling with sheetrock. Mud and tape
joints.
Additional comments: Permit for patch of ceiling shall be obtained
Location: Stairway Fire Door by room 330
Comments: Repair fire door. There is a gap at bottom of door. Must
completely seal
GENERATED ON 6/24/25, 3:22 PM
4 OF 8
Fail
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Comments: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent
smokelfire from inflitrating fire rated coridoor.
GENERATED ON 6/24125, 3:22 PM
5 OF 8
Fail
Fail
Fail
Fail
Fail
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: obtain permit and inspections
Location: Entire Second Floor
Comments: verify all removed smoke seals have been replaced on
second floor. Also 4th floor and all other smoke sweeps added to
bottom of doors must be verified as listed for fire doors and
inspected.
Location: West 3rd floor storage room fire door
Comments: repair door. Fire Door must completely self -close and
latch
Location: 3rd Floor West stair fire door
Comments: Repair door. Fire door must completly self -close and
latch.
Location: 2nd Floor laundry inside door
Comments: Repair fire door. Fire door must completely self -close and
latch. Upper part of door does not properly seal.
GENERATED ON 6/24/25, 3:22 PM 6 OF 8
Fail
Fail
Fail
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
Chapter 14
Fire alarm system tested at least annually by licensed
contractor
Location: Room 202
Comments: repair door . Fire door must completely self -close and
latch.
Location: 2nd Floor East Electrical Room
Comments: Repair door .Inside fire door must completly self -close
and latch. Repair smoke seal
Additional comments: Door to hallway failed to latch.
Location: Annual Fire Alarm Inspection
Comments: Provide current semi-annual fire alarm inspection report
with all discrepancies corrected. Currently 106 days past due.
Contractor must upload online to the compliance engine.
GENERATED ON 6/24/25, 3:22 PM
7 OF 8
Statement of Fees
FEE
Invoice Date Inspection Fee
N/A $200.00
Date Paid Amount Paid
Invoice Number
NIA
Check Number
N/A
Transaction Number
N/A
GENERATED ON 6/24/25, 3:22 PM 8 OF 8