COMMERCIAL INSPECTION - 407 E PARK AVE - 6-17-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
9492
07/09/2025
08/12/2025
2026-00000006
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
„ins peetio -Repo
Elk's Club - 407 E Park AVE, BLDt 407 E Park Ave, Waterloo IA 50703
INSPECTfQNDETAIJ„S
Inspection Date /'Inspection Type
06/17/2025 ( Annual Inspection (1Yr)
Other Inspectors
N/A
Vg'
425 E.3rd Street
Inspection Number
14015
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
0 55
0 10 ® 11
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Brad Baldwin - 06/18/2025 @ 12:23
$100 annual inspection fee
Baldwin - 06/18 • @ 12:23
-Commercial Fire Inspector £€" brad.baldwin@waterloo-ia.org a€" Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
07/1412025
Brad Baldwin - 06/18/2025 @ 12:23
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday a€" Friday, 9:00 a.m. a€" 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -inspection
fees start at $100, then $150, and $200 for all subsequent re -inspections.
Brad Baldwin - 06/23/2025 @ 07:42
Corrected during inspection: (A) Park Ave lounge bar area, removed multi -plug cord. (B) Brass lounge, removed multi -plug cord. (C) Stag Bar, removed
multi -plug cord from TV. (D) Removed multi -plug cord from organ
Brad Baldwin - 06123/2025 @ 07:42
Kitchen hood suppression system due for inspection 8/27/25.
SIGNATURES
Contact signature Inspector signature
Sherri Simon
CHECKLISTS
No signature
Report completed post inspection
Date: Brad Baldwin 06/23/2025
GENERATED ON 6/23/25, 7:48 AM 1 OF 6
Emergency Equipment
Status Code
Fail
1203.2.6
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Statue Code
Fail
304.3.1
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Fire Service Features
States Code
Fail
EXD
509.2
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
509.2
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Kitchen Up
Comments: Repair or replace exit sign that failed to illuminate during
testing
Description
Location: Kitchen Up
Comments: Provide listed container for oily rag disposal
Description
Location: Garage pull station
Comments: Remove obstructions to clear path to fire alarm pull
station.
Location: Down kitchen
Comments: Remove obstructions in front of hood suppression pull
station, maintain clear path.
GENERATED ON 6/23/25, 7:48 AM
2 OF 6
Additional Codes
Status Gode
Fail
O
Fail
0
5303.5.3
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellersa€ ""
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
907.8.4
The building owner shall be responsible to maintain the fire
and life safety systems in an operable condition at all times.
Service personnel shall meet the qualification requirements
of NFPA 72 for inspection, testing and maintenance of such
systems. Records of inspection, testing and maintenance
shall be maintained.
De
ptlo
Location: Liquor storage room
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: Red stag brass lounge storage closet
Comments: Repair or replace smoke detector "S-27" hanging by
wires, loose to box.
GENERATED ON 6/23/25, 7:48 AM
3 OF 6
Electrical Safety
-` umu*s Code
Fail
Fail
603.2
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.5
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
retocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: Walk-in freezer near garage
Comments: Repair or replace damaged protective wiring jacket to
freezer door.
Location: Park Ave lounge bar area
Comments: Remove multi -plug adapter from beverage fridge. Fridge
shall be directly plugged in to wall outlet.
GENERATED ON 6/23/25, 7:48 AM
4 OF 6
Portable Fire Extingusihers
Status Code
Fail
C
Fail
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturerd€TM's
installation instructions.
Description
Location: All fire extinguishers
Comments: Provide annual service to extinguishers, due by end of
June 2025.
Location: Kitchen Up
Comments: Provide and install "K Guard" fire extinguisher on wall
bracket. Extinguisher shall be no less than 4" from the floor, no more
than 5' in height from the floor.
GENERATED ON 6/23/25, 7:48 AM 5 OF 6