COMMERCIAL INSPECTION - 1501 E SAN MARNAN DR - 6-17-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 100,000
OCCUPANCY FEE
Total Price
$600.00
$10.00
CUSTOMER #'
4661
BILLING DATE
07/09/2025
DUE DATE
08/12/2025
INVOICE #
2026-00000024
CHARGES
$610.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
S610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
-Inspect • Report
Target Super Store 1501 E San Marnan DR, BLDG 1501 E San Marnan Dr, Waterloo
IA 50702
INSPECTION - r LS
inspection Date
06/17/2025
Brad Baldwin
Other Inspectors
NIA
Inspection Type
425 E. 3rd Street
Inspection Number
14075
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 56
Passed codes
NEXT STEPS
0 11
Failed codes
9
N/A codes
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Brad Baldwin - 06118/2025 @ 07:47
(,,,....___
$610 annual inspection fee
Brad Baldwin - 06/18/2025 @ 07:48
-Commercial Fire Inspector a€" brad.baldwin@waterloo-ia.org a€" Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
07/09/2025
Brad Baldwin - 06/1812025 @ 07:48
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday a€" Friday, 9:00 a.m. a€" 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -inspection
fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Kyle (2025) floor manager
CHECKLISTS
EJ3
Date: Brad Baldwin 06/18/2025
GENERATED ON 6/18/25, 9:05 AM 1 OF 5
Means of Egress
Status Code
Fail
1010.1.3
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
Fail
1203.4.3
Records of the inspection, testing and maintenance of
emergency and standby power systems shall include the date
of service, name of the servicing technician, a summary of
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
1203.4.3
Records of the inspection, testing and maintenance of
emergency and standby power systems shall include the date
of service, name of the servicing technician, a summary of
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
Description
Location: Near aisle B
Comments: Repair or replace exit door that failed to open without
special force or knowledge. (West door)
Description
Location: Emergency lighting & exit lights
Comments: Provide current annual emergency exit and egress light
testing with all discrepancies corrected. Include signature and date.
Location: Emergency power generator
Comments: Service/load bank testing of generator 382 days past due
as of 6/18/25. Provide service to generator, report of service and load
bank test shall be uploaded to Compliance Engine.
GENERATED ON 6/18/25, 9:05 AM 2 OF 5
Fire Sprinkler System
Status Code
Fail
Fail
5.2.1
Sprinklers shall be inspected at least annually by licensed
contractor
903.3.3
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Additional Codes
Status Code
Fail
Fail
603.9.2
Portable, electric space heaters shall be plugged directly into
an approved receptacle.
606.3.1
The ventilation system in connection with hoods shall be
operated at the required rate of air movement, and grease
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
Commercial Cooking Hood Suppression System
Status Code
Fail
Fail
a
606.3.3
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
606.3.3.3
Records for inspections shall state the individual and
company performing the inspection, a description of the
inspection and when the inspection took place. Records for
cleanings shall state the individual and company performing
the cleaning and when the cleaning took place. Such records
shall be completed after each inspection or cleaning and
maintained.
Description
Location: Sprinkler system
Comments: Provide correction to deficiency noted in report uploaded
in Compliance Engine. Report of correction must be uploaded by
contractor once completed.
Location: 2nd floor Onan generator room
Comments: Remove dust and all obstructions to sprinkler heads
Description
Location: Ray Echols office
Comments: Remove space heater from power strip.
Location: Deli kitchen
Comments: Repair or replace damaged kitchen exhaust hood filter
Description
Location: Kitchen exhaust cleaning
Comments: Cleaning 309 days past due as of 6/18/25. Provide
cleaning of exhaust system, report of cleaning shall be uploaded to
Compliance Engine.
Location: Kitchen hood fire suppression inspection
Comments: Provide kitchen hood exhaust system fire suppression
inspection report with all discrepancies corrected. Currently 140 days
past due as of 6/18/25. Contractor must upload online to the
Compliance Engine.
GENERATED ON 6/18/25, 9:05 AM 3 OF 5
Fire Resistant Construction Maintenance
Status Code
Fail
704.1
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall, 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
Status Code
Fail
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Electrical equipment room near check lane storage
Comments: Replace missing ceiling tiles.
Descript
Location: All fire extinguishers
Comments: Provide annual service to fire extinguishers, due by end
of June 2025.
GENERATED ON 6/18/25, 9:05 AM
4 OF 5
Statement of Fees
FEE
Invoice Date Inspection Fee
N/A $610.00
Invoice Number
NIA
Date Paid Amount Paid
Check Number
N/A
Transaction Number
N/A
GENERATED ON 6/18/25, 9:05 AM 5 OF 5