COMMERCIAL INSPECTION - 324 FLETCHER AVE - 6-16-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3360
07/09/2025
08/12/2025
2026-00000015
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection --Report
Kwik'PR&#�W 324 Fletcheh AVE, BLDG 324 Fletcher Ave, Waterloo IA 50701
INSPECTIO _
nspectian Date
06116/2025
cad Inspec .r
Brad Baldwin
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
14146
Shift Station Unit
N/A NIA NIA
SUMMARY OF INSPECTION
052
d 9 ®17
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL OTES
Brad Baldwin - 06/1712025 @ 08:
80.00 annual inspection fe
4
Brad Baldwin - 06/17/2025 @ 08:15
-Commercial Fire Inspector a€" brad.baldwin@waterloo-ia.org a€" Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
07/15/2025
Brad Baldwin - 06/17/2025 @ 08:15
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday a€" Friday, 9:00 a.m. a€" 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -inspection
fees start at $100, then $150, and $200 for all subsequent re -inspections.
Brad Baldwin - 06118/2025 @ 07:45
Violations corrected during inspections: (A)Extension cord from behind coffee machines ran through kitchen doorway to fan removed.
Brad Baldwin - 06123/2025 @ 14:41
Use of disposable kitchen rags shall be routinely discarded out of the building to avoid from potential spontaneous ignition in the building.
Brad Baldwin - 06/23/2025 @ 14:42
Kitchen exhaust hood cleaning due 9/6/25. Hood suppression system due 915125
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Alicia (2025) District Manager Date: Brad Baldwin 06/2312025
GENERATED ON 6/23/25, 2:50 PM 1 OF 7
CHECKLISTS
Additional Codes
Status Code
Fail
102.4
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Emergency Equipment
Status Code
Fail
1203.2.6
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Back storage room
Comments: Obtain proper permits and inspection of installed water
heater.
Description
Location: Back storage exit door
Comments: Repair or replace exit sign and emergency lighting that
failed to stay lit during testing.
GENERATED ON 6/23/25, 2:50 PM 2 OF 7
Electrical Safety
Status, Curie
Fail
0
Fail
0
Fail
603.2.2
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Outlet behind ATM at front of building
Comments: Provide proper outlet cover missing.
Location: Back storage area near water heater
Comments: Provide proper plug for opening in top of outlet box.
Location: South exterior of carwash building
Comments: Provide proper cover to outlet
GENERATED ON 6/23/25, 2:50 PM 3 OF 7
Fail
Fail
0
603.4
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Back storage area
Comments: Remove obstructions within 36" in front of electrical
panels.
Location: Office near checkout area
Comments: Remove obstructions in front of electrical panel within
36"
GENERATED ON 6/23/25, 2:50 PM
4 OF 7
Fail
603.4
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Electrical Panel "F"
Comments: Remove bun rack and maintain 36" clearance in front of
panel
GENERATED ON 6/23/25, 2:50 PM 5 OF 7
Portable Fire Extingusihers
Status Code
Fail
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Near diesel & natural gas pumps
Comments: Provide documentation of service to fire extinguishers.
GENERATED ON 6/23/25, 2:50 PM
6 OF 7