COMMERCIAL INSPECTION - 3910 UNIVERSITY AVE - 4-22-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24208
05/20/2025
06/25/2025
2025-00000346
$80.00
Less Prepayment
Total Due
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Walgreens - 3910 University AVE, BLDG 3910 University Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
04/22/2025
Lead Inspector
JEFF SIEBEL
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift
N/A
425 E. 3rd Street
Inspection Number
13674
Station Unit
N/A N/A
SUMMARY OF INSPECTION
033
Passed codes
NEXT STEPS
0 6
Failed codes
34
NIA codes
Please direct questions about your Inspection to:
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org, 3192301224
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $80.00
Invoice Number Check Number Transaction Number
N/A N/A NIA
GENERAL NOTES
JEFF SIEBEL - 04/23/2025 @ 14:09
annual inspection $80
SIGNATURES
Contact signature Inspector signature
Toni Franklin
CHECKLISTS
Means of Egress
04/23/2025 JEFF SIEBEL
Status Code Description
Fail 1010.1.3
Ff
GENERATED ON 4/23/25, 9:34 AM
Reinspection Date
0511312025
Location: exit door from restroom hall REPEAT VIOLATION
04/2312025
1 OF 3
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
1203.2.15
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fire Alarm System
Comments: Exit door must unlatch and swing to full open with less
than 15# force.
Description
Location: by main electric panels
Comments: repair egress lights
Status Code Description
Fail Chapter 14
Fire alarm system tested at least annually by licensed Location: Fire Alarm
contractor
Fire Sprinkler System
Comments: Inspection report from 2/11/25 lists discrepancies.
Contractor must upload corrections online to the compliance engine.
Status Code Description
Fail 5.2.1
0 Sprinklers shall be inspected at least annually by licensed Comments: Fire Sprinkler report from 2/11/25 lists discrepancies.
contractor Contractor must upload corrections online to the compliance engine.
Fire Service Features
Status Code Description
Fail 509.2
0 Approved access shall be provided and maintained for all fire Location: Fire Alarm Panel
protection system equipment to permit immediate safe Comments: remove obstructions to fire alarm panel, maintain a
operation and maintenance of such equipment. Storage, trash minimum of 36" clearance at all times.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Fire Resistant Construction Maintenance
Status
Code Description
Fail 705.2.4
GENERATED ON 4/23/25, 9:34 AM
2 OF 3
Swinging fire doors shall close from the full -open position Location: Fire Alaarm Panel Room
and latch automatically.
Comments: Fire door must completetly self -close and latch. Must
remain closed at all times. If desired to be kept open must close on
fire alarm signal.