HomeMy WebLinkAbout421 OAK AVEINVOICE DATE ,
DUE DATE
INVOICE #
TOTAL DUE
05/20/2025
06/25/2025
2025-00000340
$80.00
Customer #: 23235
THE ROSE OF WATERLOO
ATTN: DIANE MURPHY - OPEN ARMS
421 OAK AVE
WATERLOO, IA 50703
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 421 OAK AVE - 5-8-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23235
05/20/2025
06/25/2025
2025-00000340
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
The Rose - 421 Oak AVE, BLDG 421 Oak Ave, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
05/08/2025
Lead Inspector
Inspection Type
Residential Common Areas Inspection
425 E. 3rd Street
Inspection Number
13206
Shift Station Unit
JEREMIAH VANDYKE N/A N/A N/A
Otherinspectors
Brad Baldwin
SUMMARY OF INSPECTION
026 02 Q3
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $80.00
Reinspection Date
06107/2025
Invoice Number Check Number Transaction Number
N/A N/A N/A
GENERAL NOTES
JEREMIAH VANDYKE - 05/08/2025 @ 20:39
Fire extinguishers serviced by Continental Fire Jan 2025.
JEREMIAH VANDYKE - 05/08/2025 @ 20:41
Generator serviced by Hawkeye Electrical contractors of Cedar Rapids. 3/3/2025.
JEREMIAH VANDYKE - 05/08/2025 @ 20:42
Dryers cleaned by AKA 9/4/2024. Invoice #11982
JEREMIAH VANDYKE - 05/08/2025 @ 20:42
/10/2025 S - 5 Year Sprinkler CONTINENTAL FIRE SPRINKLER CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/08/2025 @ 20:42
4/10/2025 S - (Semi -Annual) Fire Sprinkler CONTINENTAL FIRE SPRINKLER CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/08/2025 @ 20:43
1/7/2025 S - Kitchen Hood Suppression CONTINENTAL FIRE SPRINKLER CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/08/2025 @ 20:43
117/2025 S - (Annual) Fire Alarm CONTINENTAL FIRE SPRINKLER CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/08/2025 @ 20:43
1/7/2025 S - (Annual) Kitchen Exhaust CONTINENTAL FIRE SPRINKLER CO. Reviewed Compliant
GENERATED ON 5/8/25, 3:47 PM 1 OF 2
JEREMIAH VANDYKE - 05/08/2025 @ 20:43
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday &C" Friday, 8:00 a.m. a€" 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be
performed the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. "****Re
inspection fees may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 05/08/2025 @ 20:43
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org &€" Work: 319-291-4460 - CeII: 319-883-1615
JEREMIAH VANDYKE - 05/08/2025 @ 20:45
Inspection Fee = $80.00 (To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature
NA
Gladys Rainey
CHECKLISTS
Date: JEREMIAH VANDYKE
Residential Common Areas Inspection
Status
Fail
O
Fail
Code
1104.5
Where means of egress illumination is provided, the power
supply for means of egress illumination shall normally be
provided by the premises&€T" electrical supply. In the event
of power supply failure, illumination shall be automatically
provided from an emergency system for the following
occupancies where such occupancies require two or more
means of egress: 1.Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a
place of worship and having an occupant Toad of less than
300. 2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants. 3.Group E in interior exit
access and exit stairways and ramps, corridors, windowless
areas with student occupancy, shops and laboratories.
4.Group F having more than 100 occupants. Exception:
Buildings used only during daylight hours and that are
provided with windows for natural light in accordance with
the International Building Code . 5.Group I. 6.Group M.
Exception: Buildings less than 3,000 square feet (279 m2) in
gross sales area on one story only, excluding mezzanines.
7.Group R-1. Exception: Where each sleeping unit has direct
access to the outside of the building at grade. 8.Group R-2.
Exception: Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
705.2.4
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Near room 205
05/08/2025
Comments: Egress light tested and failed. Send picture after repair
319-883-1615.
Location: Near room 316 hallway double doors.
Comments: Send video after repairing/adjustment. 319-883-1615
GENERATED ON 5/8/25, 3:47 PM
2 OF 2