COMMERCIAL INSPECTION - 610 E 4TH ST - 5-9-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000 HH
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
11098
05/20/2025
06/25/2025
2025-00000351
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Renaissance Park Apartments - 610 E 4th ST, BLDG 610 E 4th St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
05/09/2025
Lead Inspector
JEREMIAH VANDYKE
Inspection Type
Residential Common Areas Inspection
OrherInspectors
NIA
425 E. 3rd Street
Inspection Number
14043
Shift Station Unit
N/A N/A NIA
SUMMARY OF INSPECTION
0 25
Passed codes
NEXT STEPS
0 5 0 3
Failed codes N/A codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
FEE
Invoice Date Inspection Fee
NIA $100.00
Date Paid Amount Paid
Invoice Number
NIA
GENERAL NOTES
JEREMIAH VANDYKE - 05/09/2025 @ 19:52
Fire extinguishers serviced by Proshield Nov. 2024.
Check Number
NIA
JEREMIAH VANDYKE - 05/09/2025 @ 19:53
Last dryer cleaning logged and recorded 1/5/2025. Need to maintain dryer cleaning log.
JEREMIAH VANDYKE - 05/09/2025 @ 19:53
9/4/2024 S - (Annual) Fire Alarm COMMUNITY ELECTRIC/PRIMARY SYSTEMS Reviewed Compliant
JEREMIAH VANDYKE - 05/09/2025 @ 19:58
Reinspection Date
06108/2025
Transaction Number
NIA
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday a€" Friday, 8:00 a.m. A€" 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be
performed the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. *****Re
inspection fees may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 05/09/2025 @ 19:58
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org A€" Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 05/09/2025 @ 19:58
Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
SIGNATURES
Contact signature
GENERATED ON 5/9/25, 2:59 PM
Inspector signature
1 OF 3
No signature
NA
vp
Vicki Seichter Date: JEREMIAH VANDYKE 05109/2025
CHECKLISTS
Residential Common Areas Inspection
Status
Fail
0
Fail
Fail
Fail
Code Description
1104.5
Where means of egress illumination is provided, the power
supply for means of egress illumination shall normally be
provided by the premisesaCr" electrical supply. In the event
of power supply failure, illumination shall be automatically
provided from an emergency system for the following
occupancies where such occupancies require two or more
means of egress: 1.Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a
place of worship and having an occupant load of Tess than
300. 2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants. 3.Group E in interior exit
access and exit stairways and ramps, corridors, windowless
areas with student occupancy, shops and laboratories.
4.Group F having more than 100 occupants. Exception:
Buildings used only during daylight hours and that are
provided with windows for natural Tight in accordance with
the International Building Code . 5.Group 1. 6.Group M.
Exception: Buildings less than 3,000 square feet (279 m2) in
gross sales area on one story only, excluding mezzanines.
7.Group R-1. Exception: Where each sleeping unit has direct
access to the outside of the building at grade. 8.Group R-2.
Exception: Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
Location: South Stairwell between floors 3 & 4 and 4 & 5 egress
lights.
Comments: Tested egress lights and failed. Send picture of working
egress light to 319-883-1615.
Location: Sprinkler and Standpipe inspection past due.
Comments: Contact sprinkler contractor for inspection as soon as
possible.
Location: Boiler inspection report.
Comments: Need copy of last boiler inspection report. Discussed
with Mario on what he needs to maintain on site for boilers, I advised
him to discuss with boiler contractor on what needs to be recorded
and logged.
Location: Rated fire doors in stairways and apartments.
GENERATED ON 5/9/25, 2:59 PM 2 OF 3
Fail
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
906.1
Portable fire extinguishers shall be installed in all of the
following locations: 1.In new and existing Group A, B, E, F, H,
I, M, R-1, R-2, R-4 and S occupancies. Exceptions: 1.In Group
R-2 occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C. 2.In Group E
occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C. 3. In storage areas of Group
S occupancies where forklift, powered industrial truck or
powered cart operators are the primary occupants, fixed
extinguishers, as specified in NFPA 10, shall not be required
where in accordance with all of the following: 3.1. Use of
vehicle -mounted extinguishers shall be approved by the fire
code official. 3.2. Each vehicle shall be equipped with a 10-
pound, 40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use. 3.3. Not less than
two spare extinguishers of equal or greater rating shall be
available on -site to replace a discharged extinguisher. 3.4.
Vehicle operators shall be trained in the proper operation, use
and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30
feet (9144 mm) distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group I-
1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed. 4.On each floor of structures under
construction, except Group R-3 occupancies, in accordance
with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but
not limited to laboratories, computer rooms and generator
rooms, where required by the fire code official. Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.
Comments: Need to remove the paint from Fire rated tags on door
and frames.
Location: Rooftop penthouse.
Comments: Fire extinguisher is past due in penthouse. Need to have
serviced and re tagged.