COMMERCIAL INSPECTION - 2225 E SHAULIS RD - 4-16-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10030
05/20/2025
06/25/2025
2025-00000343
$100.00
Less Prepayment
Total Due — >
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE 10°
INSPECTION REPORT
LOST ISLAND WATERPARIC 2225 E SHAULIS RD, BLDG 222S E SHAULIS RD, WATERLOO 0
50702
)U
DETAILS
Inspection Date: 04/16/2025 I Inspection Type: Annual Inspection (1Yr) Inspection Number: 13809 Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 37 I Violations: 8 I N/A Codes: 31
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Maintenance Building
Original Comment: repair exit/egress light above exterior door.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Sales East - South Door
Original Comment: repair exit/egress light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Office East Door
Original Comment: Repair exit/egress light
Printed on 04/17/2025 @ 09:39
Page 1 of 4
STATUS CODE DESCRIPTION
/AIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
FAI L
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: Merchandise room
Original Comment: Repair exit light
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Coaster QUE
Original Comment: Replace missing waterproof outlet cover
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not Tess than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: Castaway Bathroom Electrical Room
Original Comment: Maintain minimum 36" clearance to all trasformer and all
electrical equipment.
Printed on 04/17/2025 @ 0939
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 904.13.5.2 - Extinguishing Automatic fire -extinguishing systems shall be serviced not less frequently than
system service. every six months and after activation of the system. Inspection shall be by
qualified individuals, and a certificate of inspection shall be forwarded to the fire
code official upon completion.
FAI L
Location: All buildings hood fire suppression systems
Original Comment: Provide current semi-annual kitchen hood fire suppression
inspection reports with all discrepancies corrected. Currently 14 days past due.
Contractor must upload online to the compliance engine.
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
GENERAL NOTES
JEFF SIEBEL - 04/17/2025 @ 08:55
JEFF SIEBEL - 04/17/2025 @ 09:05
REINSPECTION DATE
05/06/2025
CONTACT SIGNATURE
Jesse Henry
Signed on: 04/17/2025 @ 09:38
Location: Maintenance Builidng
Original Comment: Installing contractor must obtain a permit for new panel and
must call for final inspection and acceptance testing.
Annual Inspection $100