COMMERCIAL INSPECTION - 1815 LA PORTE RD - 5-6-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6647
05/20/2025
06/25/2025
2025-00000342
$80.00
Less Prepayment
Total Due -->
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Wendy's - 1815 La Porte RD, BLDG 1815 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
05/06/2025
Lead Inspector
JEREMIAH VANDYKE
inspection Type
Annual Inspection (1Yr)
vo'n
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1120
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
042
Passed codes
NEXT STEPS
0 4
Failed codes
27
NIA codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
FEE
Invoice Date Inspection Fee
NIA $80.00
Date Paid Amount Paid
Reinspection Date
06105/2025
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERAL NOTES
JEREMIAH VANDYKE - 05/06/2025 @ 20:36
4/1/2025 S - (Semi -Annual) Kitchen Exhaust GETZ FIRE EQUIPMENT CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/06/2025 @ 20:37
2/20/2025 S - Kitchen Hood Suppression HAWKEYE FIRE & SAFETY CO. Reviewed Compliant
JEREMIAH VANDYKE - 05/06/2025 @ 20:37
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday a€" Friday, 8:00 a.m. A€" 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be
performed the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. "****Re
inspection fees may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 05/06/2025 @ 20:37
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org A€" Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 05/06/2025 @ 20:43
Inspection Fee = $80.00 (To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
GENERATED ON 5/6/25, 3:44 PM 1 OF 3
No signature
Person not available for signature
Jacque Behrens - District manager Date:
CHECKLISTS
Emergency Equipment
Status Code
Fail
Documentation
Status
Fail
JEKEMIAH VANUYKE U5/Uti/'LU2b
1203.2.6
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
Code
406.3
Employees shall be trained in fire prevention, evacuation and
fire safety in accordance with Sections 406.3.1 through
406.3.4.
Commercial Cooking Hood Suppression System
Status
Fail
0
Code
906.4.2
Where hazard areas include deep fat fryers, listed Class K
portable fire extinguishers shall be provided as follows: 1.For
up to four fryers having a maximum cooking medium capacity
of 80 pounds (36.3 kg) each: one Class K portable fire
extinguisher of a minimum 1.5-gallon (6 L) capacity. 2.For
every additional group of four fryers having a maximum
cooking medium capacity of 80 pounds (36.3 kg) each: one
additional Class K portable fire extinguisher of a minimum
1.5-gallon (6 L) capacity shall be provided. 3.For individual
fryers exceeding 6 square feet (0.55 m2) in surface area:
Class K portable fire extinguishers shall be installed in
accordance with the extinguisher manufacturers€'"s
recommendations.
Portable Fire Extingusihers
Status
Fail
0
Code
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
Description
Location: Exit/Egress light near fryers and ice machine.
Comments: Tested exit/egress light that failed. Will need to be
repaired or replaced.
Description
Location: Records of training for grease fire and use of hood fire
suppresion and Class K extinguisher.
Comments: Records of training for grease fire and use of hood fire
suppresion and Class K extinguisher.
Description
Location: Silver Class K fire extinguisher sign.
Comments: Silver class K fire extinguisher needs new sign above it
and PLACED HIGHER UP. Had a hard time locating during the
inspection.
Description
Location: Red fire extinguisher failed. It was tagged Feb. 2025 by
Hawkeye fire and safety.
Comments: Will need to replace out of service fire extinguisher.
GENERATED ON 5/6/25, 3:44 PM 2 OF 3
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 5/6/25, 3:44 PM 3 OF 3