COMMERCIAL INSPECTION - 250 WESTFIELD AVE - 11-12-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 100,000
OCCUPANCY FEE
Total Price J
$600.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23522
11/19/2024
12/22/2024
2025-00000205
$610.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
COURTYARD BY MARRIOT, 250 WESTFIELD AVE, BLDG 250 WESTFIELD AVE, WATERLOO IA
50701
DETAILS
Inspection Date: 11/12/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 15431 ( Shift: N/A j Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A I Fee: $610.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 ( Passed Codes: 48 I Violations: 12 I N/A Codes: 16
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Light # 11
Original Comment: Repair exit light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: exit light #614 by room 630
Original Comment: repair exit light
Printed on 11/15/2024 @ 15:22
Page 1 of 6
STATUS CODE DESCRIPTION
FAI L 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAI L
FAI L
Location: Entire Building
Original Comment: Provide documentation that all emergency exit and egress
lights have been tested and repaired. Thanks
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
Location: Room 341
Original Comment: repair smoke detector that is hanging by wires.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Telecom room by 207
Original Comment: Properly mount power strip to wall . Power strip must not
hang by cords.
Printed on 11/15/2024 @ 15:22
Page 2of6
STATUS CODE DESCRIPTION
FAIL 603.5.2 - Application and Relocatable power taps and current taps shall be directly connected to a
usePower supply. permanently installed receptacle. Exceptions: 1. Where approved for use in a
Group A occupancy or in a meeting room in a Group B occupancy, not more than
five relocatable power taps shall be permitted to be connected together or
connected to an extension cord for temporary use to supply power to electronic
equipment. 2. Current taps and relocatable power taps shall not be required to
connect directly to a permanently installed receptacle outlet where used for 90
days or less for the purpose of testing the performance of such devices.
Location: General Manager Office
Original Comment: Refrigerator and Microwave each must plug directly into
permanent wall outlet.
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
FAI L
Location: Carry over from 2023 annual report. Kitchen hood exhaust system
cleaning inspection report
Original Comment: Provide corrections for 3 deficiencies on report from AKA
dated 7/8/24 .
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Mechanical room by room 601
Original Comment: repair door. Fire door must completely self -close and latch.
Printed on 11/15/2024 @ 15:22
Page 3of6
STATUS CODE DESCRIPTION
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Telecom room 6th floor by pool equipment room
Original Comment: Repair door. Fire door must completely self -close and latch.
FAI L
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Room 441
Original Comment: repiair door . Fire door must completely self -close and latch.
FAIL 903.3.3 - Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance
with the applicable automatic sprinkler system standard that is being used.
Automatic sprinklers shall be installed in or under covered kiosks, displays,
booths, concession stands or equipment that exceeds 4 feet (1219 mm) in width.
Not less than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible fibers. Exception:
Kitchen equipment under exhaust hoods protected with a fire -extinguishing
system in accordance with Section 904.
Location: Laundry Room
Original Comment: clear dryer lint and other debris from fire sprinkler heads.
Printed on 11/15/2024 @ 15:22
Page 4of6
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: Not Provided
Original Comment: Provide annual service for fire extinguishers
GENERAL NOTES
JEFF SIEBEL -11 /15/2024 @ 15:00 Annual inspection $610
REINSPECTION DATE
12/03/2024
CONTACT SIGNATURE
Ben Chase
Signed on: 11/15/2024 @ 15:21
n
Printed on 11/15/2024 @ 15:22
Page 5 of 6
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11 /15/2024 @ 15:21
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 11 /152024 @ 15:22
Page 6 of 6