COMMERCIAL INSPECTION - 1402 LOGAN AVE - 11-21-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
24606
BILLING DATE
12/04/2024
DUE DATE
01/08/2025
INVOICE #
2025-00000208
CHARGES
Less Prepayment
Total Due —�
City of Waterloo
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
NULL, BROWNSTONE, 1402 LOGANAVE, BLDG 1402 LOGANAVE, WATERLOO LA S0703
DETAILS
V'Y (\Qe.u)
Inspection Date: 11/21/2024 j Inspection Type: Annual Inspection (1Yr) I Inspection Number: 436 I Shift: N/A J Station: N/A
Unit: N/A I Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A ( Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 54 I Violations: 3 I N/A Codes: 18
STATUS CODE DESCRIPTION
FAIL 606.2 - Where required. A Type I hood shall be installed at or above all commercial cooking appliances
and domestic cooking appliances used for commercial purposes that produce
grease vapors. Exceptions: 1.Factory-built commercial exhaust hoods that are
listed and labeled in accordance with UL 710, and installed in accordance with
Section 304.1 of the International Mechanical Code, shall not be required to
comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4 and
507.5 of the International Mechanical Code. 2.Factory-built commercial cooking
recirculating systems that are listed and labeled in accordance with UL 710B, and
installed in accordance with Section 304.1 of the International Mechanical Code,
shall not be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8,
507.3.1, 507.3.3, 507.4 and 507.5 of the International Mechanical Code. Spaces in
which such systems are located shall be considered to be kitchens and shall be
ventilated in accordance with Table 403.3.1.1 of the International Mechanical
Code. For the purpose of determining the floor area required to be ventilated,
each individual appliance shall be considered as occupying not less than 100
square feet (9.3 m2). 3.Where cooking appliances are equipped with integral
down -draft exhaust systems and such appliances and exhaust systems are listed
and labeled for the application in accordance with NFPA 96, a hood shall not be
required at or above them. 4.A Type I hood shall not be required for an electric
cooking appliance where an approved testing agency provides documentation
that the appliance effluent contains 5 mg/m3 or less of grease when tested at an
exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with UL 710B.
Location: Basement kitchen above electric stove with no commercial hood or
suppression system.
Original Comment: Per IFC code 606.2 and the Iowa State Marshal division policy
for the rquirement of hood suppression system requirements in the building.
Printed on 11/22/2024 @ 14:20
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
Location: Clothes dryers located in basement.
Original Comment: Clothes Dryer Exhaust Duct system must be cleaned from the
dryer to the outside DOCUMENTED by who and when serviced.
FAIL 906.4 - Cooking equipment Fire extinguishers provided for the protection of cooking equipment shall be of
fires. an approved type compatible with the automatic fire -extinguishing system agent.
Cooking equipment involving solid fuels or vegetable or animal oils and fats shall
be protected by a Class K-rated portable extinguisher in accordance with
Sections 906.1, Item 2, 906.4.1 and 906.4.2 as applicable.
Location: Basement kitchen area.
Original Comment: Class K fire extinguisher needed and installed.
GENERAL NOTES
JEREMIAH VANDYKE - 11/22/2024 @ 13:44 08/20/2024 S - (Quarterly) Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE • 11/22/2024 @ 13:44 07/30/2024 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE -11 /22/2024 @ 13:45 Fire extinguishers serviced by Proshield May 2024.
JEREMIAH VANDYKE - 11/22/2024 @ 14:16 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
Printed on 11/22/2024 @ 14:20
Page 2 of 3
GENERAL NOTES
JEREMIAH VANDYKE - 11/22/2024 @ 14:16
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 11/22/2024 @ 14:16 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 11/22/2024 @ 14:16 Inspection Fee = $80.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
12/22/2024
CONTACT SIGNATURE
Sam Hudson Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 11/22/2024 @ 14:19