COMMERCIAL INSPECTION - 325 COMMERCIAL ST - 11-20-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 20,000
OCCUPANCY FEE
Total Price ]
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22975
12/04/2024
01/08/2025
2025-00000217
$100.00
Less Prepayment
Total Due -->
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SINGLE SPEED BREWING, 325 COMMERCIAL ST, BLDG 325 COMMERCIAL ST, WATERLOO /A
50702
DETAILS
Inspection Date: 11/20/2024 j Inspection Type: Annual Inspection (1Yr) ; Inspection Number: 11617 j Shift: N/A ! Station: N/A j
Unit: N/A j Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 41 I Violations: 14 I N/A Codes: 21
STATUS CODE DESCRIPTION
FAIL
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: By North Door by Dock
Original Comment: repair egress light
Printed on 11 /212024 @ 09:41
Page 1 of 10
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
FAIL 1203.2.6 - Exit signs.
Location: from by shuffle board to dining area
Original Comment: repair exit/egress light.
Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: South side on outside patio
Original Comment: repair exit/egress light
Printed on 11 /21 /2024 @ 09:41
Page 2 of 10
STATUS
FAIL
CODE
1203.2.6 - Exit signs.
DESCRIPTION
Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: North side outside patio
Original Comment: repair exit/egress light
Printed on 11/21/2024 @ 09:41
Page 3 of 10
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAI L
Location: Egress light above tanks in brewery
Original Comment: provide documentation of testing and repair of egress light .
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance
(no troubles, supervisory, or alarms)?
Location: On column above full kegs
Original Comment: repair damaged fire alarm horn strobe hanging off of
electrical box .
Printed on 11 /212024 @ 09:41
Page 4 of 10
STATUS
FAIL
FAI L
CODE
315.3.3 - Equipment rooms.
509.2 - Equipment access.
DESCRIPTION
Combustible material shall not be stored in boiler rooms, mechanical rooms,
electrical equipment rooms or in fire command centers as specified in Section
508.1.5.
Location: upper electrical room
Original Comment: Remove storage (boxes of materials not related to electrical
or fire equipment) from electrical room. Maintain 36" clearance to fire panel,
transformers, and electric panel
Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
Location: Dry fire sprinkler riser by empty kegs
Original Comment: Remove obstructions to dry riser. Maintain a minimum of 36"
path to and around the dry fire sprinler riser. Suggest marking floor and
installing permanent location sign above stating " Fire Sprinkler Riser " at this
time but will be mandatory if found to be repeat offense.
Printed on 11 /21 /2024 @ 09:41
Page 5 of 10
STATUS
FAIL
CODE
603.4 - Working space and
clearancesclearance.
DESCRIPTION
A working space of not Working space around electrical equipment shall be
provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: By Back door to coffee area across from big water tank.
Original Comment: remove obstructions to electric panel LVIC. maintain a
minimum of 36" clearance at all times. REPEAT VIOLATION
Printed on 11 /21 /2024 @ 09:41
Page 6 of 10
STATUS CODE DESCRIPTION
FAIL. 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
FAI L
603.5.2 - Application and
usePower supply.
Location: By Office
Original Comment: remove obstructions to the electrical panel
Relocatable power taps and current taps shall be directly connected to a
permanently installed receptacle. Exceptions: 1. Where approved for use in a
Group A occupancy or in a meeting room in a Group B occupancy, not more than
five relocatable power taps shall be permitted to be connected together or
connected to an extension cord for temporary use to supply power to electronic
equipment. 2. Current taps and relocatable power taps shall not be required to
connect directly to a permanently installed receptacle outlet where used for 90
days or less for the purpose of testing the performance of such devices.
Location: Corner Office Desk below Chalk Signs
Original Comment: Each power strip must plug directly into wall outletn not
another power strip (daisy chaining).
Printed on 11 /21 /2024 @ 09:41
Page 7 of 10
STATUS
FAIL
CODE
603.9.4 - Prohibited areas.
FAIL 903.3.3 - Obstructed
locations.
DESCRIPTION
Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: Office in Coffee Shop
Original Comment: remove electric heater or provide documentation that it is
approved for commercial use and clearances are maintained.
Automatic sprinklers shall be installed with regard to obstructions that will delay
activation or obstruct the water distribution pattern and shall be in accordance
with the applicable automatic sprinkler system standard that is being used.
Automatic sprinklers shall be installed in or under covered kiosks, displays,
booths, concession stands or equipment that exceeds 4 feet (1219 mm) in width.
Not less than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible fibers. Exception:
Kitchen equipment under exhaust hoods protected with a fire -extinguishing
system in accordance with Section 904.
Location: walk in cooler
Original Comment: remove obstructions to fire sprinkler head. Install head guard.
Really close to being knocked off today.
Printed on 11 /21 /2024 @ 09:41
Page 8 of 10
STATUS
FAIL
CODE
906.6 - Unobstructed and
unobscured.
GENERAL NOTES
JEFF SIEBEL - 11/21/2024 @ 09:40
JEFF SIEBEL - 11/21/2024 @ 09:41
REINSPECTION DATE
12/10/2024
DESCRIPTION
Portable fire extinguishers shall not be obstructed or obscured from view. In
rooms or areas in which visual obstruction cannot be completely avoided, means
shall be provided to indicate the locations of extinguishers.
Location: By empty kegs
Original Comment: remove obstructions . maintain a minimum of 36" clearance
at all times.
Annual inspection $100
kitchen hood cleaning due 12/12/24
Printed on 11/21/2024 @ 09:41
Page 9 of 10
CONTACT SIGNATURE
Alex Hottle
Signed on: 11/21/2024 @ 09:39
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/21/2024 @ 09:39
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL