COMMERCIAL INSPECTION - 228 E 4TH ST - 11-21-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price J
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
14048
12/04/2024
01/08/2025
2025-00000213
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SCREAMING EAGLE BAR & GRILL, 228E 4TH ST, BLDG 228E 4TH ST, WATERLOO IA 50703
DETAILS
Inspection Date: 11/21/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 11671 I Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A ( Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 43 I Violations: 8 I N/A Codes: 23
STATUS CODE DESCRIPTION
FAIL
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: Above ATM main floor
Original Comment: repair egress light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Abpve main entrance
Original Comment: Repair exit/egress light
FAIL 304.3.1 - Spontaneous Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in
ignition. a listed disposal container. Contents of such containers shall be removed and
disposed of daily.
Location: Kitchen
Original Comment: Provide an approved listed oily waste container with self -
closing lid for all grease laden clothes to prevent spontanious combustion.
Printed on 11/22/2024 @ 09:45
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 4.9 - Support of nonsprinkler Sprinkler system components shall not be used to support non -sprinkler system
system components components unless expressly permitted by NFPA 13.
Location: Basement Bar Side
Original Comment: Remove tape, string and debris from fire sprinkler pipe and
hangers.
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: Electrical room by bar in basement
Original Comment: remove obstructions in front of the electrical panels. Maintain
a minimum of 36" clearance at all times.
Printed on 11/22/2024 @ 09:45
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: South basement storage room
Original Comment: remove obstructions to electric panel. Maintain a minimum of
36" clearance at all times.
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: Kitchen hood exhaust cleaning
Original Comment: Provide current semi-annual kitchen hood exhaust system
inspection report with all discrepancies corrected. Currently 15 days past due.
Contractor must upload online to the compliance engine.
FAIL 705.2.6 - Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested
annually to confirm proper operation and full closure. Records of inspections
and testing shall be maintained.
Location: kitchen fire door
Original Comment: Provide documentation of annual fire door drop test. May be
already completed just need info on paperwork or sticker.
GENERAL NOTES
Printed on 11/22/2024 @ 09:45
Page 3 of 4
JEFF SIEBEL - 11/22/2024 @ 09:41 Annual Inspection fee $80
JEFF SIEBEL -11/22/2024 @ 09:42 Fire Alarm due 12/19/24
JEFF SIEBEL -11 /22/2024 @ 09:42 Hood Suppression due 1/16/2025
REINSPECTION DATE
12/13/2024
CONTACT SIGNATURE
Jeremy Jones
Signed on: 11/22/2024 @ 09:43
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/22/2024 @ 09:43