HomeMy WebLinkAbout1925 LA PORTE RDCustomer #: 5403
BURGER KING
1925 LA PORTE RD
WATERLOO, IA 50702
INVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
12/04/2024
01/08/2025
2025-00000214
$200.00
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1925 LA PORTE RD - 11-21-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
5403
12/04/2024
01/08/2025
2025-00000214
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
BURGER KING, 1925 LA PORTE RD, BLD6 192S LA PORTE RD, WATERLOO IA S0702
DETAILS
Inspection Date: 11/21/2024 ! Inspection Type: Annual Inspection (1Yr) I Inspection Number: 9026-R4 I Shift: N/A j Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL ; Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 ( Passed Codes: 0 I Violations: 2 I N/A Codes: 0
STATUS CODE
DESCRIPTION
FAIL 606.3.3.1 - Inspection. Hoods, grease -removal devices, fans, ducts and other appurtenances shall be
inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code
official. Inspections shall be completed by qualified individuals.
Location: kitchen hood exhaust system cleaning
Original Comment: Provide current kitchen hood exhaust system cleaning
inspection report with all discrepancies corrected. Now 14 days past the 6
month. Contractor must upload online to the compliance engine. See the
attached code section in notes.
Additional Comment: Now 83 days past due. Your contractor (All Seasons I
Believe) must upload your inspection report online to the compliance engine.
FAIL 606.3.3.2 - Grease If during the inspection it is found that hoods, grease -removal devices, fans,
accumulation. ducts or other appurtenances have an accumulation of grease, such
components shall be cleaned in accordance with ANSI/IKECA C10.
Location: Kitchen exhaust hood
Original Comment: Clean grease filters. Currently oil dripping from them .
Suggest more frequent cleaning of kitchen hood exhaust system because of
heavy use.
Additional Comment: 2 filters still have grease dripping from them.
Printed on 11 /21 /2024 @ 15:03
Page 1 of 3
ii
STATUS
GENERAL NOTES
CODE
JEFF SIEBEL - 10/29/2024 @ 07:48
JEFF SIEBEL -10/29/2024 @ 07:48
JEFF SIEBEL - 10/29/2024 @ 07:48
JEFF SIEBEL - 10/29/2024 @ 07:48
DESCRIPTION
annual inspection fee $80
no change, other than grease filters missing.
Re -inspection fee $100
No change. Grease still dripping from filters and hood cleaning now past due 14 days
from 6 month. Recommend cleaning everything every 3 months.
JEFF SIEBEL - 10/29/2024 @ 07:48 See attached code section
JEFF SIEBEL -10/29/2024 @ 07:48 no reinspection fee today because of progress. Re -inspection fee of $150 will be
assesed at next inspection if not complete.
JEFF SIEBEL - 10/29/2024 @ 07:48
JEFF SIEBEL - 11 /21 /2024 @ 14:43
REINSIECTION DATE
12/17/2024
re -inspection fee $150
Re -inspection fee $200
Printed on 11 /21 /2024 @ 15:03
Page 2of3
CONTACT SIGNATURE
Rory Cagley - District manager
Signed on: 11/21/2024 @ 15:01
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 11/21/2024 @ 15:01
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
L/c ly
Printed on 11/21/2024 @ 15:03