COMMERCIAL INSPECTION - 4335 TEXAS ST - 12-6-24
[ Description'
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24613
12/16/2024
01/20/2025
2025-00000219
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
THE CEDAR CORNER, 4335 TEXAS ST, BLDG 4335 TEXAS ST, WATERLOO IA 50702
DETAILS
Inspection Date: 12/06/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 15637 j Shift: N/A j Station: N/A j
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: JEREMIAH VANDYKE I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 26 I Violations: 4 I N/A Codes: 44
STATUS CODE DESCRIPTION
FAI L
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: behind counter where pizza is planned
Original Comment: Properly mount conduit/outlet to wall
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: Kitchen hood exhaust cleaning inspection
Original Comment: Provide current semi-annual kitchen hood exhaust system
cleaning inspection with all disrepancies corrected. Currently 255 days past due.
Contractor must upload report online to the compliance engine OR permanently
disconnect and cap gas outlets
Printed on 12/09/2024 @ 11:05
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood fire suppression inspection report
Original Comment: Provide current semi-annual kitchen hood exhaust system
fire suppression inspection report with all disrepancies corrected. Currently 620
days past due. Contractor must upload report online to the compliance engine
OR permanently disconnect and cap gas outlets
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: front area and back area
Original Comment: Provide annual service for fire extinguishers
GENERAL NOTES
JEFF SIEBEL - 12/09/2024 @ 11:00 annual inspection $80
JEFF SIEBEL -12/09/2024 @ 11:03 Kitchen not to be put back into service without fire inspectors approval and kitchen
hood services brought up to date.
Printed on 12/09/2024 @ 11:05
Page 2 of 3
GENERAL NOTES
JEFF SIEBEL - 12/09/2024 @ 11:04
JEFF SIEBEL - 12/09/2024 @ 11:01
JEFF SIEBEL - 12/09/2024 @ 11:02
Air compressor and vacuum outside are currently disconnected after improper wiring
was removed.
Call fire inspector 319-230-1224 when store is organized and everything is in place
before opening.
All electrical must be installed by a licensed contractor with permits and inspections.
REINSPECTION DATE
01/03/2025
CONTACT SIGNATURE
Rewoti Adhikari
Signed on: 12/09/2024 @ 11:04
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 12/09/2024 @ 11:04