COMMERCIAL INSPECTION - 603 S HACKETT RD - 12-6-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
Total Price ]
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24136
12/16/2024
01/20/2025
2025-00000220
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
WOMEN S SHELTER SALVATION ARMY, 603 S HACKETT RD, BLDG 603 SOUTH HACKETT ROAD,
WATERLOO IA 50701
DETAILS
Inspection Date: 12/06/2024 1 Inspection Type: Annual Inspection (1Yr) Inspection Number: 15629 1 Shift: N/A Station: N/A 1
Unit: N/A 1 Lead Inspector: JEREMIAH VANDYKE 1 Other Inspectors: N/A 1 Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 1 Passed Codes: 57 1 Violations: 7 1 N/A Codes: 11
STATUS CODE DESCRIPTION
FAI L
1103.8 - Single- and multiple- Single- and multiple -station smoke alarms shall be installed in existing Group 1-1
station smoke alarms. and R occupancies in accordance with Sections 1103.8.1 through 1103.8.3.
Location: Bedroom F.
Original Comment: Smoke alarm was disconntected and not working properly.
Discussed starting a weekly log to check smokes alarms if they were
disconnected or batteries removed.
Printed on 12/06/2024 @ 16:27
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 404.2.1 - Fire evacuation Fire evacuation plans shall include the following: 1.Emergency egress or escape
plans. routes and whether evacuation of the building is to be complete by selected
floors or areas only or with a defend -in -place response. 2.Procedures for
employees who must remain to operate critical equipment before evacuating.
3.Procedures for the use of elevators to evacuate the building where occupant
evacuation elevators complying with Section 3008 of the International Building
Code are provided. 4.Procedures for assisted rescue for persons unable to use
the general means of egress unassisted. 5.Procedures for accounting for
employees and occupants after evacuation has been completed. 6.Identification
and assignment of personnel responsible for rescue or emergency medical aid.
7.The preferred and any alternative means of notifying occupants of a fire or
emergency. 8.The preferred and any alternative means of reporting fires and
other emergencies to the fire department or designated emergency response
organization. 9.Identification and assignment of personnel who can be contacted
for further information or explanation of duties under the plan. 10.A description
of the emergency voice/alarm communication system alert tone and
preprogrammed voice messages, where provided.
FAI L
Location: Fire evacuation plans.
Original Comment: Confirm that bedrooms have fire evacution plans in
bedrooms and common spaces.
5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Location: 5 year sprinkler inspection due.
Original Comment: 5 year sprinkler inspection due and shows 205 days past due.
Please contact sprinkler contractor to address.
FAIL 509.1 - Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements fire protection systems
shall be identified for the use of the fire department. Approved signs required to
identify fire protection system equipment and equipment location shall be
constructed of durable materials, permanently installed and readily visible.
Location: Outside fence on south of building.
Original Comment: Need sign stating "FDC" that is made of durable material and
readible from road placed on outside of fence facing street.
Printed on 12/06/2024 @ 16:27
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 509.2 - Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
FAI L
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
Location: FDC access through fence on south side of building.
Original Comment: Need to address access for fire department through fence for
FDC and maintaining panic hardware.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Garage area.
Original Comment: Refridgerators and freezer must be plugged directly into wall
outlet and not extension cords.
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
Location: Clothes dryers cleaning log.
Original Comment: Clothes Dryer Exhaust Duct system must be cleaned from the
dryer to the outside DOCUMENTED by who and when serviced.
GENERAL NOTES
JEREMIAH VANDYKE - 12/06/2024 @ 15:51 Fire extinguishers servicws by Superior Fire July 2024.
JEREMIAH VANDYKE - 12/06/2024 @ 15:58 2/7/2024 S - (Annual) Fire Alarm ABSOLUTE SECURITY CEDAR VALLEY LLC Reviewed
Compliant Compliant
Printed on 12/06/2024 @ 16:27
Page 3 of 4
GENERAL NOTES
JEREMIAH VANDYKE - 12/06/2024 @ 16:24 Discussed installing signage stating "Kitchen Fan must be on when stove is in use" on
kitchen hoods.
JEREMIAH VANDYKE - 12/06/2024 @ 16:25
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE -12/06/2024 @ 16:25 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 12/06/2024 @ 16:26 Inspection Fee = $80.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
01/05/2025
CONTACT SIGNATURE
Martin Ainsworth - maintenance Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 12/06/2024 @ 16:26
QUESTIONS AIOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 12/06/2024 @ 16:27
Page 4 of 4