COMMERCIAL INSPECTION - 213 E 5TH ST - 12-3-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23164
12/19/2024
01/25/2025
2025-00000228
$80.00
Less Prepayment
Total Due —►
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
THE COMFORT ZONE, 213 E STH ST, BLD6 213 - 219E STH ST, WATERLOO IA 50703
DETAILS
S\q,
Inspection Date: 12/03/2024 ( Inspection Type: Annual Inspection (1Yr) Inspection Number: 11655 Shift: N/A j Station: N/A
Unit: N/A I Lead Inspector: JEREMIAH VANDYKE Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 55 I Violations: 4 I N/A Codes: 15
STATUS CODE DESCRIPTION
FAI L
FAI L
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Behind bar by little refrigerators.
Original Comment: 1. Power strip plugged into power strip. 2. Little refridgerators
plugged into powerstrip. Discussed getting an electrician to add more outlets for
direct plug in of appliances/fridge.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Behind DJ booth.
Original Comment: Power strips plugged into other power strip needs removed.
Printed on 12/04/2024 @ 16:17
Page 1 of 4
STATUS
FAIL
CODE
606.3.3 - Cleaning.
DESCRIPTION
Hoods, grease -removal devices, fans, ducts and other appurtenances shall be
cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3.
Location: Kitchen hood cleaning
Original Comment: Hood cleaning report needs to be uploaded to our
Compliance Engine asap by hood cleaning contractor.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Near men's restroom
Original Comment: Ceiling tile needs replaced.
Printed on 12/04/2024 @ 16:17
Page 2 of 4
STATUS
GENERAL NOTES
CODE
DESCRIPTION
JEREMIAH VANDYKE - 12/04/2024 @ 16:13 9/17/2024 5 - Kitchen Hood Suppression SUPERIOR FIRE PROTECTION EQUIPMENT
Reviewed Compliant
JEREMIAH VANDYKE - 12/04/2024 @ 16:14 Fire extinguishers serviced by Superior Fire Sept. 2024.
JEREMIAH VANDYKE - 12/04/2024 @ 16:16
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 12/04/2024 @ 16:16 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 12/04/2024 @ 16:16 Inspection Fee = $80.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
01/03/2025
CONTACT SIGNATURE
Tommy Mccelllan-bey
Reason for not collecting a signature: NA
Printed on 12/04/2024 @ 16:17