COMMERCIAL INSPECTION - 2332 FALLS AVE - 5-15-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20423
06/12/2025
07/15/2025
2025-00000401
$80.00
Less Prepayment
Total Due —÷
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Re ,ort
Metro 66 - 2332 Falls AVE, BLDG�2332 Falls Ave, Waterloo IA 50701
I PECTION DETAILS
nspection Date
05/15/2025
d Inspector
Brad :a •win
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
JEFF SIEBEL
425 E. 3rd Street
Inspection Number
13708
Shift Station Unit
N/A N/A N/A
SUMMARY OF INSPECTION
069
Passed codes
NEXT STEPS
0 6
Failed codes
Please direct questions about your Inspection to:
Brad Baldwin
brad.baldwin@waterloo-ia.org, 31929143
FEE
Invoice Date
N/A
Inspection Fee
$80.00
Date Paid Amount Paid
Reinspection Date
06/12/2025
Invoice Number ♦ eck Number Transaction Number
N/A N/A NIA
GENERAL NOTES
Brad Baldwin - 05/15/2025 @ 17:01
$80 annual inspection
Brad Baldwin - 05/15/2025 @ 20:25
Moved combustibles away from cooking appliance in storage room during 5/15/25 inspection. Clearances shall be maintained.
SIGNATURES
Contact signature Inspector signature
Lisa
CHECKLISTS
Means of Egress
Status
Fail
O
No signature
Report completed post inspection
Code
13B
Date: Brad Baldwin 05/15/2025
1032.3
A means of egress shall be free from obstructions that would
prevent its use, including the accumulation of snow and ice.
Description
Location: Rear (north) exit door.
GENERATED ON 5/15/25, 3:37 PM
1 OF 3
Emergency Equipment
Status Code
Fail
1203.2.15
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Additional Codes
Comments: Remove obstructions to exit path or remove exit signage
with wires properly contained in covered box. Per Building Official,
Greg Ahlhelm, exit not required. Door locked during time of
inspection, door is to remain unlocked during business hours if exit
signage is present.
Description
Location: Front entrance exit sign
Comments: Emergency lights on exit sign failed testing. Repair or
replace.
Stratus Code Description
Fail 2305.5
l^_l Approved portable fire extinguishers complying with Section Location: Within 75 ft of fuel pumps
906 with a minimum rating of 2-A:20-B:C shall be provided
and located such that an extinguisher is not more than 75 feet Comments: Provide properly serviced extinguisher within 75 feet of
(22 860 mm) from pumps, dispensers or storage tank fill -pipe fuel pumps installed within 4 inches of floor and maximum 5 feet in
height.
openings.
Fail
5303.5.3
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellersa€"
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Electrical Safety
Status
Fail
0
Code
603.2
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Portable Fire Extingusihers
Status
Fail
Code
906.2
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
Location: Storage room
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Description
Location: West exterior conduit elbow
Comments: Install cover to conduit elbow properly
Description
Location: Behind counter
GENERATED ON 5/15/25, 3:37 PM
2 OF 3
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group I-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Comments: Annual fire extinguisher service past due. Last serviced
March 2024.