COMMERCIAL INSPECTION - 926 LINN ST - 2-27-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
22283
BILLING DATE
03/11/2025
DUE DATE
04/15/2025
INVOICE #
2025-00000293
CHARGES
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SPEEDY MART, 926 LINN ST, BLDG 926 LINN ST, WATERLOO ►A 50703
DETAILS
Inspection Date: 02/27/2025 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 13318 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 28 I Violations: 7 I N/A Codes: 40
STATUS CODE DESCRIPTION
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: exit door to outside from kitchen
Original Comment: repair exit door. Must unlatch with less than 15# force and
swing to full open.
Printed on 02/28/2025 @ 11:43
Page 1 of 5
STATUS CODE DESCRIPTION
il. 102.3 - Change of use or
occupancy.
A change of occupancy shall not be made unless the use or occupancy is made to
comply with the requirements of this code and the International Existing Building
Code . Exception: Where approved by the fire code official, a change of occupancy
shall be permitted without complying with the requirements of this code and the
International Existing Building Code , provided that the new or proposed use or
occupancy is Tess hazardous, based on life and fire risk, than the existing use or
occupancy.
Location: Kitchen
Original Comment: Remove cot and bedding immediately. No sleeping or living in
building allowed
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
FAIL 1203.2.6 - Exit signs.
Location: Electrical for new warmer at front of store
Original Comment: Obtain electrical permit and inspections for new warmer
installed without permit.
Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Back door from 924
Original Comment: repair exit/egress light
Printed on 02/28/2025 01 11:43
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: outlet cover on front of building
Original Comment: replace missing water proof outlet cover.
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: employee only area street side of score
Original Comment: remove obstructions to electric panel. Ladder and others.
Printed on 02/28/2025 @ 11:43
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood exhaust cleaning inspection report
Original Comment: Provide current semi-annual kitchen hood exhaust system
inspection report with all discrepancies corrected. Currently Out of Service/past
due, and was not supposed to be used without permission from fire inspector.
Contractor must upload online to the compliance engine.
GENERAL NOTES
JEFF SIEBEL - 02/28/2025 @ 11:39 annual inspection $80
JEFF SIEBEL - 02/28/2025 @ 11:40 Remove all bedding and cots from building immediately . No sleeping allowed at any
time.
REINSPECTION DATE
03/20/2025
CONTACT SIGNATURE
DILAWAR KHAN 2023
Signed on: 02/28/2025 @ 11:41
INSPECTOR SIGNATURE
JEFF SIEBEL