COMMERCIAL INSPECTION - 230 E RIDGEWAY AVE - 2-24-25
FOR BILLING INQUIRY: (319)291-4323
[ Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
5687
BILLING DATE
03/11/2025
DUE DATE
04/15/2025
INVOICE #
2025-00000288
CHARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
IIM LIND, 230 E RIDGEWAYAVE, BLDG 230 E RIDGEWAYAVE, WATERLOO IA 50702
DETAILS
Inspection Date: 02/24/2025 I Inspection Type: Annual Inspection (1ber: 12525 Shift: N/A I Station: N/A
Unit: N/A j Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 35 I Violations: 4 I N/A Codes: 36
STATUS CODE DESCRIPTION
Fait 2305.5 - Fire extinguishers.
FAIL
5303.5.3 - Securing
compressed gas containers,
cylinders and tanks.
Approved portable fire extinguishers complying with Section 906 with a minimum
rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not
more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill -pipe
openings.
Location: For gas pumps
Original Comment: Provide 2A 20BC fire extinguisher with 75 feet or install
signage directing you to proper fire extinguisher.
Compressed gas containers, cylinders and tanks shall be secured to prevent
falling caused by contact, vibration or seismic activity. Securing of compressed
gas containers, cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object with one or more
restraints. 2.Securing containers, cylinders and tanks on a cart or other mobile
device designed for the movement of compressed gas containers, cylinders or
tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container
filling or servicing facilities or in sellers' warehouses not open to the public.
Nesting shall be allowed provided that the nested containers, cylinders or tanks,
if dislodged, do not obstruct the required means of egress. 4.Securing of
compressed gas containers, cylinders and tanks to or within a rack, framework,
cabinet or similar assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of examination, filling, transport or
servicing.
Location: parts room by batteries.
Original Comment: Secure compressed tanks with chain to stationary object.
Printed on 02/24/2025 @ 15:27
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Lottery machine in store
Original Comment: remove extension cord from lottery machine. You may use a
circuit protected power tap.
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: Not Provided
Original Comment: Provide annual service for fire extiniushers.
6ENER4L NOTES
JEFF SIEBEL - 02/24/2025 @ 15:24 annual inspection $80
JEFF SIEBEL - 02/24/2025 @ 15:24 dryer vent cleaned by Chimney Sweeps 1/10/25
Printed on 02/24/2025 @ 15:27
Page 2 of 3
REINSPECTION DATE
03/25/2025
CONTACT SIGNATURE
Kerry Elliot
Signed on: 02/24/2025 @ 15:25
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/24/2025 @ 15:25