COMMERCIAL INSPECTION - 3628 KIMBALL AVE - 3-21-25
FOR BILLING INQUIRY: (319)291-4323
[ Description
REINSPECTION 3
Total Price j
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24657
03/28/2025
04/30/2025
2025-00000307
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
R SMOKES PLUS, 3628 KIMBALL AVE, BLDG 3628 KIMBALL AVE, WATERLOO /A S0701
DETAILS
Inspection Date: 03/21/2025 E Inspection Type: Annual Inspection (1Yr) I Inspection Number: 1138-R3 ! Shift: N/A ( Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 1 I Passed Codes: 0 I Violations: 8 ( N/A Codes: 0
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: Not Provided
Original Comment: Obtain permits and inspections for all electrical and building
work completed without and any future work.
Printed on 03/24/202 ; @ 09:38
Page 1 of 7
STATUS
FAI L
CODE
1032.2 - Reliability.
DESCRIPTION
Required exit accesses, exits and exit discharges shall be continuously
maintained free from obstructions or impediments to full instant use in the case
of fire or other emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be used for any purpose
that interferes with a means of egress.
Location: Front door and aisles between display cases.
Original Comment: Remove power cords from in front of front door and install
electrical between display cases in accordance with electrical code
Printed on 03/24/2025 @ 09:38
Page 2 of 7
STATUS CODE DESCRIPTION
FAIL 1032.2 - Reliability. Required exit accesses, exits and exit discharges shall be continuously
maintained free from obstructions or impediments to full instant use in the case
of fire or other emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be used for any purpose
that interferes with a means of egress.
FAIL
FAIL
308.1.5 - Location near
combustibles.
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
Location: Back hall
Original Comment: Remove obstructions to rear exit. No storage allowed.
Open flames such as from candles, lanterns, kerosene heaters and gas -fired
heaters shall not be located on or near decorative material or similar
combustible materials.
Location: Through out store
Original Comment: Open flames (incense) prohibited near combustibles.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Behind counter
Original Comment: remove multi -plug adapter and extension cords
Printed on 03/24/2025 @ 09:38
Page 3 of 7
STATUS
FAIL
FAI L
CODE
603.6 - Extension cords.
603.6 - Extension cords.
DESCRIPTION
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Behind counter
Original Comment: remove extension cords and install permanent power with
proper permit and inspections.
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: By front door
Original Comment: Remove extension cords at front of store, including one
crossing exit door. Cooler must plug directly into permanent wall outlet. Install
permanent wall outlet with permits and inspections.
Printed on 03/24/2025 @ 09:38
Page 4 of 7
STATUS
FAIL
CODE
906.1 - Where required.
DESCRIPTION
Portable fire extinguishers shall be installed in all of the following locations: 1.In
new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exceptions: 1.In Group R-2 occupancies, portable fire extinguishers shall be
required only in locations specified in Items 2 through 6 where each dwelling unit
is provided with a portable fire extinguisher having a minimum rating of 1-A:10-
B:C. 2.In Group E occupancies, portable fire extinguishers shall be required only
in locations specified in Items 2 through 6 where each classroom is provided with
a portable fire extinguisher having a minimum rating of 2-A:20-B:C. 3. In storage
areas of Group S occupancies where forklift, powered industrial truck or powered
cart operators are the primary occupants, fixed extinguishers, as specified in
NFPA 10, shall not be required where in accordance with all of the following: 3.1.
Use of vehicle -mounted extinguishers shall be approved by the fire code official.
3.2. Each vehicle shall be equipped with a 10-pound, 40A:80B:C extinguisher
affixed to the vehicle using a mounting bracket approved by the extinguisher
manufacturer or the fire code official for vehicular use. 3.3. Not less than two
spare extinguishers of equal or greater rating shall be available on -site to replace
a discharged extinguisher. 3.4. Vehicle operators shall be trained in the proper
operation, use and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30 feet (9144 mm)
distance of travel from commercial cooking equipment and from domestic
cooking equipment in Group 1-1; 1-2, Condition 1; and R-2 college dormitory
occupancies. 3.In areas where flammable or combustible liquids are stored, used
or dispensed. 4.On each floor of structures under construction, except Group R-3
occupancies, in accordance with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by the fire
code official. Exception: Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where a portable fire
extinguisher suitable to the hazard of the location is provided on the vehicle of
visiting personnel.
Location: Front and Back areas
Original Comment: Properly mount 2 2A 10BC currently serviced Fire
extinguishers 4" to5' above the floor in an accesible location . One in front area
and one in back area.
Printed on 03/24/2025 @ 09:38
Page 5 of 7
STATUS
CODE
GENERAL NOTES
JEFF SIEBEL - 02/24/2025 @ 09:27
JEFF SIEBEL - 02/24/2025 @ 09:27
JEFF SIEBEL - 02/24/2025 @ 09:27
JEFF SIEBEL - 02/24/2025 @ 09:27
JEFF SIEBEL - 03/24/2025 @ 09:26
JEFF SIEBEL - 03/24/2025 @ 09:22
REINSPECTION DATE
04/11/2025
CONTACT SIGNATURE
Lafi Alagrabawi
Signed on: 03/24/2025 @ 09:22
DESCRIPTION
re -inspection fee $150
annual inspection $80
Re -inspection fee $100. No progress
Provide corrections to avoid progressive re -inspection fees, $150 next, and $200 for
every inspection after.
Re -inspection fee $200
No permits obtained at this time.
Printed on 03/24/202 5 @ 09:38
Page 6 of 7
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/24/2025 @ 09:22