COMMERCIAL INSPECTION - 2034 LA PORTE RD - 3-19-25
FOR BILLING INQUIRY: (319)291-4323
[ Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
03/28/2025
04/30/2025
2025-00000303
$100.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
qb5
HAMPTON INN & SUITES, 2034 LA PORTE RD, BLDG 2034 LA PORTE RD, WATERLOO IA S0702
DETAILS
Inspection Date: 03/19/2025 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 13671-R3 I Shift: N/A ( Station: N/A
Unit: N/A Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 12 I Passed Codes: 0 I Violations: 20 I N/A Codes: 0
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
FAI L
Location: Entire buiding
Original Comment: Obtain permits and inspections for all work concerning fire
door repair, replacement smoke seals, all hardware replaced. Please see original
attached email with codes concerning information requiered for fire door
hardware. Please contact Building Official Greg Ahlhelm with questions. 319-291-
4319
Additional Comment: Obtain permits for all work concerning fire doors including
smoke seals including bottom, new hardware installation and fire door
replacement.
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
Location: Room 128
Original Comment: repair smoke detector. Smoke detector and lights hanging by
wires.
Additional Comment: unabel to access room to verify 3/19/25
Printed on 03/2412025 @ 08:t0
Page 1 of 9
STATUS CODE DESCRIPTION
FAIL 5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
FAI L
FAIL
Location: Annual Fire Sprinkler Deficiency
Original Comment: Provide current annual fire sprinkler report with all
discrepancies corrected. Current report lists deficiencies . Contractor must
upload corrections online to the compliance engine.
Additional Comment: Still 2 deficiencies from 6/25/24 inspection. Contractor must
post corrections online to the compliance engine.
5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Location: Annual Standpipe insepction deficiencies
Original Comment: Provide current annual fire sprinkler stand pipe inspection
report wth all discrepancies corrected. Current report lists 2 discrepancies.
Contractor must upload corrections online to the compliance engine.
Additional Comment: Stand pipe still showing 2 deficiencies. Contractor must
upload corrections to the compliance engine.
5.2.1.1.5 - Missing Escutcheons and coverplates for recessed, flush, and concealed sprinklers shall
escutcheons be replaced if found missing during the inspection.
Location: Room 300
Original Comment: replace missing eschutcheon above sink
Additional Comment: Unable to access room.
FAIL 506.2 - Key box maintenance. The operator of the building shall immediately notify the fire code official and
provide the new key where a lock is changed or rekeyed. The key to such lock
shall be secured in the key box.
Location: KNOX BOX
Original Comment: Update fire department access keys for every space after
remodel
Additional Comment: Please call for new keys placement.
Printed on 03/24/2025 @ 08:10
Page 2 of 9
STATUS CODE DESCRIPTION
FAIL 507.5.3 - Private fire service Private fire service mains and water tanks shall be periodically inspected, tested
mains and water tanks. and maintained in accordance with NFPA 25 at the following intervals: 1.Private
fire hydrants of all types: Inspection annually and after each operation; flow test
and maintenance annually. 2.Fire service main piping: Inspection of exposed,
annually; flow test every 5 years. 3.Fire service main piping strainers: Inspection
and maintenance after each use. Records of inspections, testing and
maintenance shall be maintained.
Location: Private Fire Hydrant Deficiency
Original Comment: Provide current semi-annual fire hydrant inspection and
testing report with all discrepancies corrected. Current report lists deficiency.
Contractor must upload corrections online to the compliance engine.
Additional Comment: Repair fire hydrant deficiencies. Contractor must post
correctons online to the compliance engine.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Stairway Fire Door by room 330
Original Comment: Repair fire door. There is a gap at bottom of door. Must
completely seal
Additional Comment: Still gap at bottom, No hardware installed
Printed on 03/24/2025 @ 08:10
Page 3 of 9
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5,Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Original Comment: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent smoke/fire from
inflitrating fire rated coridoor.
Additional Comment: Need Inspections
Printed on 03/24/2025 @ 08:10
Page 4 of 9
STATUS CODE DESCRIPTION
i=AI L 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. S.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire second floor guest fire doors
Original Comment: Install approved smoke seal in all fire door openings that has
been removed including stair doors and utility areas. Check all other floors
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1 Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Guest Computer Room
Original Comment: patch sheetrock ceiling with sheetrock. Mud and tape joints.
Printed on 03/24/2025 @ 08:10
Page 5 of 9
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: IT equipment room in offices
Original Comment: replace missing ceiling tiles.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: obtain permit and inspections
Printed on 03/24/2025 @ 08:10
Page 6 of 9
STATUS CODE DESCRIPTION
FAIL 705.2.4 - Door operation. Swinging fire doors shall dose from the full -open position and latch
automatically.
FAIL
FAIL
FAI L
Location: West 3rd floor storage room fire door
Original Comment: repair door. Fire Door must completely self -close and latch
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: 3rd Floor West stair fire door
Original Comment: Repair door. Fire door must completly self -close and latch.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: 2nd Floor laundry inside door
Original Comment: Repair fire door. Fire door must completely self -close and
latch. Upper part of door does not properly seal.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Room 202
Original Comment: repair door . Fire door must completely self -close and latch.
Printed on 03/24/2025 @ 08:10
Page 7 of 9
STATUS CODE DESCRIPTION
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
FAIL
FAIL
Location: 2nd Floor East Electrical Room
Original Comment: Repair door .Inside fire door must completly self -close and
latch. Repair smoke seal
Additional Comment: Still gap at the bottom.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Room 319 Fire Door and smoke detector
Original Comment: Fire door must completely self -close and latch. Smoke
detector not working
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
GENERAL NOTES
JEFF SIEBEL - 02/14/2025 @ 15:29
JEFF SIEBEL - 02/14/2025 @ 15:29
JEFF SIEBEL - 02/14/2025 @ 15:29
Location: Annual Fire Alarm Inspection
Original Comment: Provide current semi-annual fire alarm inspection report with
all discrepancies corrected. Currently 106 days past due. Contractor must upload
online to the compliance engine.
Provide corrections to avoid re -inspection fees
Annual inspection $235
Provide corrections to avoid re -inspection fees.
Printed on 03/24/2025 @ 08:10
Page 8 of 9
GENERAL NOTES
JEFF SIEBEL - 03/24/2025 @ 08:02 Re -inspection fee $100
JEFF SIEBEL - 03/24/2025 @ 08:06 Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for
completion of fire door certifications.
REINSPECTION DATE
04/17/2025
CONTACT SIGNATURE
Mitch Goodrich - Maintenance
Signed on: 03/24/2025 @ 08:06
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/24/2025 @ 08:06