COMMERCIAL INSPECTION - 2020 BOPP ST - 3-21-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
24677
BILLING DATE
04/04/2025
DUE DATE
05/08/2025
INVOICE #
2025-00000317
CHARGES
$100.00
Less Prepayment
Total Due —►
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
aLi(0---T)
INSPECTION REPORT
RED LIGHT MARKET, 2020 BOPP ST, BLDG 2020 BOPP ST - STE 2020 BOPP ST, WATERLOO
S0702 IOU
`` j� r ^O
DETAILS
Inspection Da
Unit: N/A I L
e: 03/21 /2025 I
d Inspector: JE
Inspection Type: Annual Inspection (1Yr) I Inspection Number: 16184-R1 I Shift: N/A Station: N/A
F SIEBEL ( Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 2 I Passed Codes: 0 I Violations: 9 I N/A Codes: 0
STATUS CODE
DESCRIPTION
FAIL 1010.2.9 - Panic and fire exit Swinging doors serving a Group H occupancy and swinging doors serving rooms
hardware. or spaces with an occupant load of 50 or more in a Group A or E occupancy shall
not be provided with a latch or lock other than panic hardware or fire exit
hardware. Exceptions: 1.A main exit of a Group A occupancy shall be permitted to
have locking devices in accordance with Section 1010.2.4, Item 2 3. 2.Doors
provided with panic hardware or fire exit hardware and serving a Group A or E
occupancy shall be permitted to be electrically locked in accordance with Section
1010.2.12 or 1010.2.11. 3. Exit access doors serving occupied exterior areas shall
be permitted to be locked in accordance with Section 1010.2.4, Item 8.
4.Courtrooms shall be permitted to be locked in accordance with Section
1010.2.13, Item 3. Electrical rooms with equipment rated 1,200 amperes or more
and over 6 feet (1829 mm) wide, and that contain overcurrent devices, switching
devices or control devices with exit or exit access doors, shall be equipped with
panic hardware or fire exit hardware. The doors shall swing in the direction of
egress travel.
Location: Back door in back storeroom
Original Comment: Permanently remove barricade and brackets from exit door
or have reviewed by building official Greg Ahlhelm to deterimine if required.
Printed on 03/24/2025 @ 09:47
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 102.3 - Change of use or A change of occupancy shall not be made unless the use or occupancy is made to
occupancy. comply with the requirements of this code and the International Existing Building
Code . Exception: Where approved by the fire code official, a change of occupancy
shall be permitted without complying with the requirements of this code and the
International Existing Building Code , provided that the new or proposed use or
occupancy is less hazardous, based on life and fire risk, than the existing use or
occupancy.
FAI L
102.4 - Application of building
code.
Location: Furnace room
Original Comment: NO SLEEPING IN BUILDING. REMOVE ALL BEDDING AND
MATRESSES IMMEDIATLY.
Additional Comment: Bedding was removed on inspection 4/20/25
The design and construction of new structures shall comply with the
International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: Water heater
Original Comment: Obtain water heater permits and inspections for water
heater.
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: Three compartment sink
Original Comment: Obtain plumbing permit and inspections for sink installation
that was installed without.
Printed on 03/24/2025 @ 09:47
Page 2 of 6
STATUS
CODE
DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
code.
FAIL 1203.2.6 - Exit signs.
Location: New Wall
Original Comment: Obtain building permit and inspections for new wall
constructed without.
Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: middle of back room
Original Comment: repair egress/exit light
Printed on 03/24/2025 @ 09,47
Page 3 of 6
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: rear exit door in back room
Original Comment: repair egress exit light or request building official Greg
Ahlhelm review to see if required.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: West Exit Door
Original Comment: repair exit/egress lilght
Printed on 03/24/2025 @ 09:47
Page 4 of 6
STATUS CODE DESCRIPTION
FAIL 906.1 - Where required. Portable fire extinguishers shall be installed in all of the following locations: 1.In
new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exceptions: 1.In Group R-2 occupancies, portable fire extinguishers shall be
required only in locations specified in Items 2 through 6 where each dwelling unit
is provided with a portable fire extinguisher having a minimum rating of 1-A:10-
B:C. 2.In Group E occupancies, portable fire extinguishers shall be required only
in locations specified in Items 2 through 6 where each classroom is provided with
a portable fire extinguisher having a minimum rating of 2-A:20-B:C. 3. In storage
areas of Group S occupancies where forklift, powered industrial truck or powered
cart operators are the primary occupants, fixed extinguishers, as specified in
NFPA 10, shall not be required where in accordance with all of the following: 3.1.
Use of vehicle -mounted extinguishers shall be approved by the fire code official.
3.2. Each vehicle shall be equipped with a 10-pound, 40A:80B:C extinguisher
affixed to the vehicle using a mounting bracket approved by the extinguisher
manufacturer or the fire code official for vehicular use. 3.3. Not less than two
spare extinguishers of equal or greater rating shall be available on -site to replace
a discharged extinguisher. 3.4. Vehicle operators shall be trained in the proper
operation, use and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30 feet (9144 mm)
distance of travel from commercial cooking equipment and from domestic
cooking equipment in Group 1-1; 1-2, Condition 1; and R-2 college dormitory
occupancies. 3.In areas where flammable or combustible liquids are stored, used
or dispensed. 4.On each floor of structures under construction, except Group R-3
occupancies, in accordance with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by the fire
code official. Exception: Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where a portable fire
extinguisher suitable to the hazard of the location is provided on the vehicle of
visiting personnel.
EENERAL NOTES
JEFF SIEBEL - 02/21/2025 @ 10:47
JEFF SIEBEL - 03/24/2025 @ 09:45
REINSPECTION DATE
04/10/2025
Location: Entire Store
Original Comment: Mount currently serviced fire extinguisher 4" to 5' above the
floor in an accesible location within 75' of any location in store and back room
areas.
Annual Inspection $80
re -inspection $100
Printed on 03/24/2025 @ 09:47
Page 5 of 6
CONTACTSIGNATURE
Kumba-store owner
Signed on: 03/24/2025 @ 09:45
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/24/2025 @ 09:45