COMMERCIAL INSPECTION - 400 E TOWER PARK DR - 4-10-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 100,000
OCCUPANCY FEE
Total Price
$600.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #`'
CHARGES
12176
04/16/2025
05/20/2025
2025-00000324
$610.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
S610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
LOWES, 400 E TOWER PARK DR, BLDG 400 E TOWER PARK DR, WATERLOO IA S0701
DETAILS
1
Inspection Date: 04/10/2025 I Inspection Type: Annual Inspection (1 Yr) I Inspection Number: 6187 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL j Other Inspectors: N/A I Fee: $610.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 33 I Violations: 26 I N/A Codes: 30
STATUS CODE
FAIL
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
DESCRIPTION
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Breakroom
Original Comment: Exit door must unlatch and swing to full open with less than
15# force. Will not open at all
Printed on 04/11/2025 @ 15:26
Page 1 of 13
STATUS CODE DESCRIPTION
I AIL 1010.1.3 - Door opening
force Forces to unlatch and
open doors.
FAIL
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Exit door 89
Original Comment: repair exit door that won't open. Door must unlatch and
swing to full open with less than 15# force.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Recieving door 65
Original Comment: repair exit door that won't open. Door must unlatch and
swing to full open with less than 15# force.
Printed on 04/11/2025 @ 15:26
Page 2 of 13
STATUS CODE DESCRIPTION
FAIL
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Door 101 Garden Center
Original Comment: repair exit door that won't open. Door must unlatch and
swing to full open with less than 15# force.
Printed on 04/11/2025 @ 15:26
Page 3 of 13
STATUS CODE DESCRIPTION
FAIL 1010.2.13.1 - Delayed egress The delayed egress locking system shall be installed and operated in accordance
locking system. with all of the following: 1.The delay electronics of the delayed egress locking
system shall deactivate upon actuation of the automatic sprinkler system or
automatic fire detection system, allowing immediate, free egress. 2.The delay
electronics of the delayed egress locking system shall deactivate upon loss of
power controlling the lock or lock mechanism, allowing immediate free egress.
3.The delayed egress locking system shall have the capability of being deactivated
at the fire command center and other approved locations. 4.An attempt to
egress shall initiate an irreversible process that shall allow such egress in not
more than 15 seconds when a physical effort to exit is applied to the egress side
door hardware for not more than 3 seconds. Initiation of the irreversible process
shall activate an audible signal in the vicinity of the door. Once the delay
electronics have been deactivated, rearming the delay electronics shall be by
manual means only. Exception: Where approved, a delay of not more than 30
seconds is permitted on a delayed egress door. 5.The egress path from any point
shall not pass through more than one delayed egress locking system. Exceptions:
1.In Group 1-1, Condition 2, Group 1-2 or 1-3 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds.
2.In Group 1-1, Condition 1 or Group 1-4 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds
and the building is equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. 6.A sign shall be provided on the door and
shall be located above and within 12 inches (305 mm) of the door exit hardware:
Exception: Where approved, in Group 1 occupancies, the installation of a sign is
not required where care recipients who, because of clinical needs, require
restraint or containment as part of the function of the treatment area. 6.1.For
doors that swing in the direction of egress, the sign shall read: "PUSH UNTIL
ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.2.For doors that
swing in the opposite direction of egress, the sign shall read: "PULL UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.3.The sign shall comply
with the visual character requirements in ICC A117.1. 7.Emergency lighting shall
be provided on the egress side of the door. 8.The delayed egress locking system
units shall be listed in accordance with UL 294.
Location: Door 91 Garden
Original Comment: Replace missing delayed exit signage as outlined in code.
Printed on 04/11/2025 @ 15:26
Page 4 of 13
STATUS CODE DESCRIPTION
FAIL 1010.2.13.1 - Delayed egress The delayed egress locking system shall be installed and operated in accordance
locking system. with all of the following: 1.The delay electronics of the delayed egress locking
system shall deactivate upon actuation of the automatic sprinkler system or
automatic fire detection system, allowing immediate, free egress. 2.The delay
electronics of the delayed egress locking system shall deactivate upon loss of
power controlling the lock or lock mechanism, allowing immediate free egress.
3.The delayed egress locking system shall have the capability of being deactivated
at the fire command center and other approved locations. 4.An attempt to
egress shall initiate an irreversible process that shall allow such egress in not
more than 15 seconds when a physical effort to exit is applied to the egress side
door hardware for not more than 3 seconds. Initiation of the irreversible process
shall activate an audible signal in the vicinity of the door. Once the delay
electronics have been deactivated, rearming the delay electronics shall be by
manual means only. Exception: Where approved, a delay of not more than 30
seconds is permitted on a delayed egress door. 5.The egress path from any point
shall not pass through more than one delayed egress locking system. Exceptions:
1.In Group 1-1, Condition 2, Group 1-2 or 1-3 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds.
2.In Group 1-1, Condition 1 or Group 1-4 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds
and the building is equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. 6.A sign shall be provided on the door and
shall be located above and within 12 inches (305 mm) of the door exit hardware:
Exception: Where approved, in Group I occupancies, the installation of a sign is
not required where care recipients who, because of clinical needs, require
restraint or containment as part of the function of the treatment area. 6.1.For
doors that swing in the direction of egress, the sign shall read: "PUSH UNTIL
ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.2.For doors that
swing in the opposite direction of egress, the sign shall read: "PULL UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.3.The sign shall comply
with the visual character requirements in ICC A117.1.7.Emergency lighting shall
be provided on the egress side of the door. 8.The delayed egress locking system
units shall be listed in accordance with UL 294.
Location: Exit 19 Garden
Original Comment: replace missing delayed egress signage as outlined in code
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Aisle 55
Original Comment: repair damaged exit light.
Printed on 04/11/2025 @ 15:26
Page 5 of 13
STATUS CODE DESCRIPTION
lL 1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Aisle 56/22
Original Comment: repair damaged exit light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Aisle 36
Original Comment: Repair damaged exit light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Aisle 5 by door 91
Original Comment: Repair2 damaged exit lights
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: Generator Load Bank Test and Engine Service
Original Comment: Provide documentation of bi-annual generator load bank test
and current engine service records for emergency generator.
Printed on 04/11/2025 @ 15:26
Page 6 of 13
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: Exit and Egress Light emergency light testing
Original Comment: Provide documentation of testing and repair of all exit and
egress lighting with signature and date.
FAIL 5003.5 - Hazard identification Unless otherwise exempted by the fire code official, visible hazard identification
signs. signs as specified in NFPA 704 for the specific material contained shall be placed
on stationary containers and above -ground tanks and at entrances to locations
where hazardous materials are stored, dispensed, used or handled in quantities
requiring a permit and at specific entrances and locations designated by the fire
code official.
Location: Outside gate of hazardous material storage.
Original Comment: replace faded NFPA 704 placard with correct signage and
updated ratings.
FAIL 509.1 - Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements fire protection systems
shall be identified for the use of the fire department. Approved signs required to
identify fire protection system equipment and equipment location shall be
constructed of durable materials, permanently installed and readily visible.
Location: Fire Sprinkler Room Door
Original Comment: Install permanent signage stating " FIRE SPRINKLER RISER
ROOM" on outside of door.
Printed on 04/11/2025 @ 15:26
Page 7 of 13
STATUS CODE DESCRIPTION
FAIL
FAI L
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
Location: Fire Sprinkler Room
Original Comment: Remove obstructions( barricade cones) to fire sprinkler valves
and all equipment.
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: Outside door 67 on outside wall
Original Comment: Repair outlet and conduit by properly mounting and
containing all exposed wiring.
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: Outside of door 108
Original Comment: Repair outlet and conduit and properly contain wires.
Printed on 04/11/2025 @ 15:26
Page 8 of 13
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not Tess than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70.2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: Front entry
Original Comment: remove obstruction to electrical panel (wheel chair)
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Front end snack storage
Original Comment: remove extension cord running through door way
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: Training Room
Original Comment: remove portable heater
Printed on 04/11/2025 @ 15:26
Page 9 of 13
STATUS CODE DESCRIPTION
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: HR Office
Original Comment: remove portable heater.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Front IT Room
Original Comment: replace missing ceiling tile.
Printed on 04/11/2025 @ 15:26
Page 10 of 13
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Camera Room
Original Comment: replace missing ceiling tile.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Front Janitor Closet
Original Comment: replace missing ceiling tile.
Printed on 04/11/2025 @ 15:26
Page 11 of 13
STATUS CODE DESCRIPTION
705.2.2 - Labeling Where required by the fire code official, a sign shall be permanently displayed on
Requirements or near each fire door in letters not less than 1 inch (25 mm) high to read as
follows: 1.For doors designed to be kept normally open: "FIRE DOOR —DO NOT
BLOCK." 2.For doors designed to be kept normally closed: "FIRE DOOR —KEEP
CLOSED."
Location: Exterior Exit doors with faded signage.
Original Comment: Replace permanent signage on all exit doors that have faded.
FAIL 907.4.1 - Protection of fire In areas that are not continuously occupied, a single smoke detector shall be
alarm control unit. provided at the location of each fire alarm control unit, notification appliance
circuit power extenders and supervising station transmitting equipment.
Exception: Where ambient conditions prohibit installation of a smoke detector, a
heat detector shall be permitted.
GENERAL NOTES
JEFF SIEBEL - 04/11/2025 @ 15:25
JEFF SIEBEL - 04/11/2025 @ 15:25
REINSPECTION DATE
05/06/2025
CONTACT SIGNATURE
Brian Hoag
Signed on: 04/11/2025 @ 15:24
Location: Fire Alarm Control Panel Room
Original Comment: Provide required smoke detection above fire alarm control
panel.
Annual inspection fee $610
Repair exit doors that do not open imrnediatly
Printed on 04/11/2025 @ 15:26