COMMERCIAL INSPECTION - 1615 BISHOP AVE - 3-11-25
[ Description
FOR BILLING INQUIRY: (319)291-4323
REINSPECTION 1
Total Price ]
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20738
02/17/2025
03/20/2025
2025-00000267
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
B & B EAST, 1615 BISHOP AVE, BLDG 1615 BISHOP AVE, WATERLOO /A 50707
DETAILS
Inspection Date: 03/11/2025 j Inspection Type: Annual Inspection (1Yr) 1 Inspection Number: 12364-R1 I Shift: N/A Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 2 I Passed Codes: 0 I Violations: 4 1 N/A Codes: 0
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: above front door
Original Comment: Repair exit/egress light
FAIL 603.5.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
Location: walk path by display case
Original Comment: Power cord must be protected by listed cord protector.
Printed on 02/14/2025 @ 14:17
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 606.2 - Where required. A Type I hood shall be installed at or above all commercial cooking appliances
and domestic cooking appliances used for commercial purposes that produce
grease vapors. Exceptions: 1.Factory-built commercial exhaust hoods that are
listed and labeled in accordance with UL 710, and installed in accordance with
Section 304.1 of the International Mechanical Code, shall not be required to
comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4 and
507.5 of the International Mechanical Code. 2.Factory-built commercial cooking
recirculating systems that are listed and labeled in accordance with UL 710B, and
installed in accordance with Section 304.1 of the International Mechanical Code,
shall not be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8,
507.3.1, 507.3.3, 507.4 and 507.5 of the International Mechanical Code. Spaces in
which such systems are located shall be considered to be kitchens and shall be
ventilated in accordance with Table 403.3.1.1 of the International Mechanical
Code. For the purpose of determining the floor area required to be ventilated,
each individual appliance shall be considered as occupying not Tess than 100
square feet (9.3 m2). 3.Where cooking appliances are equipped with integral
down -draft exhaust systems and such appliances and exhaust systems are listed
and labeled for the application in accordance with NFPA 96, a hood shall not be
required at or above them. 4.A Type I hood shall not be required for an electric
cooking appliance where an approved testing agency provides documentation
that the appliance effluent contains 5 mg/m3 or less of grease when tested at an
exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with UL 710B.
Location: outside hood on counter
Original Comment: electric fry pan must be under kitchen hood and protected by
fire protection system.
Additional Comment: Now griddle is outside of hood and fire suppression
system.
Printed on 02/14/2025 @ 14:17
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 606.2 - Where required. A Type I hood shall be installed at or above all commercial cooking appliances
and domestic cooking appliances used for commercial purposes that produce
grease vapors. Exceptions: 1.Factory-built commercial exhaust hoods that are
listed and labeled in accordance with UL 710, and installed in accordance with
Section 304.1 of the International Mechanical Code, shall not be required to
comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4 and
507.5 of the International Mechanical Code. 2.Factory-built commercial cooking
recirculating systems that are listed and labeled in accordance with UL 710B, and
installed in accordance with Section 304.1 of the International Mechanical Code,
shall not be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8,
507.3.1, 507.3.3, 507.4 and 507.5 of the International Mechanical Code. Spaces in
which such systems are located shall be considered to be kitchens and shall be
ventilated in accordance with Table 403.3.1.1 of the International Mechanical
Code. For the purpose of determining the floor area required to be ventilated,
each individual appliance shall be considered as occupying not less than 100
square feet (9.3 m2). 3.Where cooking appliances are equipped with integral
down -draft exhaust systems and such appliances and exhaust systems are listed
and labeled for the application in accordance with NFPA 96, a hood shall not be
required at or above them. 4.A Type I hood shall not be required for an electric
cooking appliance where an approved testing agency provides documentation
that the appliance effluent contains 5 mg/m3 or less of grease when tested at an
exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with UL 710B.
Location: Kitchen hood
Original Comment: Large chicken fryer must be 6" under hood to avoid flame roll
out in the event of a fire.
GENERAL NOTES
JEFF SIEBEL - 02/14/2025 @ 14:16 re -inspection fee $100
JEFF SIEBEL - 01/29/2025 @ 15:26 annual inspection $80
JEFF SIEBEL - 01/29/2025 @ 15:26 Gas pump 2 out of service.
JEFF SIEBEL - 01/29/2025 @ 15:26 Gas Line Alarm on monitor is in alarm mode. Rectify problem.
REINSPECT/ON DATE
03/13/2025
Printed on 02/14/2025 @ 14:17
Page 3 of 4
CONTACT SIGNATURE
Muhammad Sarwar
Signed on: 02/14/2025 @ 14:11
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/14/2025 @ 14:11