COMMERCIAL INSPECTION - 117 E SAN MARNAN DR - 2-18-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
24676
BILLING DATE
02/25/2025
DUE DATE
03/30/2025
City of Waterloo
INVOICE #
2025-00000283
Less Prepayment
Total Due —�
CHARGES
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
L-ik(r)
WATERLOO FIRE RESCUE
INSPECTION REPORT
THE SPOT #3, 117 E SAN MARNAN DR, BLDG 117 E SAN MARNAN DR, WATERLOO IA 50702
DETAILS
Inspection Date: 02/18/2025 I Inspection Type: Annual Inspection (1 Yr) I Inspection Number: 16174 j Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL j Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 16 I Violations: 11 I N/A Codes: 49
STATUS CODE DESCRIPTION
FAI L
102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: storage room behind counter.
Original Comment: Stop work issued. Obtain building permit and inspections for
opening cut in wall behind counter and any electrica work completed for room
Printed on 02/19/2025 @ 12:59
Page 1 of 7
STATUS CODE
DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
FAIL 1032.2 - Reliability.
Location: Ceiling and back room
Original Comment: Obtain electrical permit and inspections for new outlets,
wiring, and lights. Have licensed electrician contact electical inspector Tim Moyer
for requirements. 319-291-4319
Required exit accesses, exits and exit discharges shall be continuously
maintained free from obstructions or impediments to full instant use in the case
of fire or other emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be used for any purpose
that interferes with a means of egress.
Location: Back exit door in back storage room
Original Comment: remove obstructions and maintain a clear path or contact
Building Official Greg Ahlhelm 319-291-4319 to review if exit required or sign may
be eliminated
Printed on 02/19/2025 @ 12:59
Page 2 of 7
STATUS CODE DESCRIPTION
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Ceililng in Store
Original Comment: Properly contain exposed wires in junction box with approved
listed covers.
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70.2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: Back room , by rear entrance and past restrooms on wall
Original Comment: remove obstructions to electrical panel. Mainain a minimum
of 36 minimum clearance.
Printed on 02/19/2025 @ 12:59
Page 3 of 7
STATUS CODE DESCRIPTION
FAIL 603.5.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
FAIL
603.6 - Extension cords.
Location: Cooler to C4 Energy Cooler
Original Comment: power strip hanging by cord. Must be properly mounted and
plugged directly into wall outlet. Coolers not allowed on power strips, must plug
directly into wall outlet.
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: To Venom Energy by Front Counter
Original Comment: Remove extension cord. Cooler must plug directly into
permanent wall outlet.
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: New storage room
Original Comment: remove extension cord. cooler must plug directly into
permanent wall outlet.
Printed on 02/19/2025 @ 12:59
Page 4 of 7
STATUS
FAI L
CODE
704.1 - Maintaining
protection.
DESCRIPTION
Where required when the building was originally constructed, materials and
systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1 Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Back room
Original Comment: replace missing ceiling tile after electrical inspections
complete.
Printed on 02/19/2025 @ 12:59
Page 5 of 7
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: all fire extinguishers
Original Comment: provide annual service for fire extinguishers. Last in 2023
FAIL 906.6 - Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In
unobscured. rooms or areas in which visual obstruction cannot be completely avoided, means
shall be provided to indicate the locations of extinguishers.
Location: back room by electrical panel
Original Comment: remove obstructions, maintain a minimum of 36" clearances.
GENERAL NOTES
JEFF SIEBEL - 02/19/2025 @ 12:58 annual inspection $80
Printed on 02/19/2025 @ 12:59
Page 6 of 7
REINSPECTION DATE
03/11/2025
CONTACT SIGNATURE
Abdul Awan
Signed on: 02/19/2025 @ 12:56
INSPECTOR S►GNATURE
JEFF SIEBEL
Signed on: 02/19/2025 @ 12:56