COMMERCIAL INSPECTION - 250 ANSBOROUGH AVE - 2-7-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 50,000
OCCUPANCY FEE
Total Price ]
$225.00
$10.00
CUSTOMER #
24040
BILLING DATE
02/25/2025
DUE DATE
03/30/2025
INVOICE #
2025-00000275
CHARGES
$23 5.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$235.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HIPPODROME AUDITORIUM, 250 ANSBOROUGH AVE, BLDG 257 ANSBOROUGH AVE,
WATERLOO IA 50701
DETAILS
Inspection Date: 02/07/2025 ! Inspection Type: Annual Inspection (1Yr) I Inspection Number: 13427 j Shift: N/A ( Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL Other Inspectors: N/A I Fee: $235.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 41 1 Violations: 8 I N/A Codes: 24
STATUS CODE DESCRIPTION
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: 2 exit doors between sections E and D
Original Comment: All doors must unlatch and swing to full open with less than
15# force.
Printed on 02/10/2025 @ 09:47
Page 1 of 4
STATUS CODE DESCRIPTION
t 1032.2 - Reliability. Required exit accesses, exits and exit discharges shall be continuously
maintained free from obstructions or impediments to full instant use in the case
of fire or other emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be used for any purpose
that interferes with a means of egress.
FAI L
Location: East Lobby Doors
Original Comment: Immediatley remove chain from exit door panic hardware.
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: M South Wall above hot tub
Original Comment: repair egress light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
FAI L
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: Above outside door by maintenance office entrance.
Original Comment: repair exit/egress light
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: storage room by visitors lockerroom
Original Comment: install dead man cover
Printed on 02/10/2025 @ 09:47
Page 2 of 4
e-
STATUS CODE DESCRIPTION
FAIL 603.5.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
Location: ticket area
Original Comment: remove rug from over power strip cord in walk path. Insall
listed cord protector cover.
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: maintenance office
Original Comment: remove portable heaters and extension cords
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: By restrooms
Original Comment: Repair ceiling with fire resistent materials(sheetrock) .
Remove sumppump and extension cords. Fire sprinkler will not function properly
without ceiling.
Printed on 02/10/2025 @ 09:47
Page 3 of 4
GENERAL NOTES
JEFF SIEBEL - 02/10/2025 @ 09:46
JEFF SIEBEL - 02/10/2025 @ 09:46
REINSPECTION DATE
02/27/2025
CONTACT SIGNATURE
Jim Koch
Signed on: 02/10/2025 @ 09:44
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/10/2025 @ 09:44
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
annual inspection $235
Fire extingiushers due in March