COMMERCIAL INSPECTION - 1016 MAYNARD - 2-13-25
FOR BILLING INQUIRY: (319)291-4323
[Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price J
$70.00
$10.00
CUSTOMER#
BILLING DATE
DUE DATE
INVOICE #
CHARGES
4428
02/25/2025
03/30/2025
2025-00000276
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
BUZZ'S BAR, 1016 MAYNARD AVE, BLDG 1016 MAYNARD AVE, WATERLOO IA S0701
DETAILS
Inspection Date: 02/13/2025 I Inspection Type: Annual Inspection (1Yr) j Inspection Number: 11889 Shift: N/A j Station: N/A
Unit: N/A ( Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A j Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 27 I Violations: 3 I N/A Codes: 43
STATUS CODE DESCRIPTION
FAIL 603.5.2 - Application and Relocatable power taps and current taps shall be directly connected to a
usePower supply. permanently installed receptacle. Exceptions: 1. Where approved for use in a
Group A occupancy or in a meeting room in a Group B occupancy, not more than
five relocatable power taps shall be permitted to be connected together or
connected to an extension cord for temporary use to supply power to electronic
equipment. 2. Current taps and relocatable power taps shall not be required to
connect directly to a permanently installed receptacle outlet where used for 90
days or less for the purpose of testing the performance of such devices.
Location: Office in basement.
Original Comment: Power strips may not be daisy chained (plugged into another
power strip). Must plug directly into wall outlet. Microwave and air fryer must
plug directly into wall outlet.
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Outside from smoke shack through door to lights on outside of shack.
Original Comment: remove extension cord
Printed on 02/1412025 @ 09:12
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL 603.8 - Temporary wiring. Temporary The use of temporary wiring for electrical power and lighting
installations shall not exceed is allowed for a period not to exceed of 90 days.
Temporary wiring methods shall meet the applicable provisions of NFPA 70.
Exception: Temporary wiring for electrical power and lighting installations is
allowed complying with the applicable provisions of NFPA 70 is permitted during
periods of construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Location: Basement
Original Comment: Decorative lights must be removed after 90 days. Remove
extension cord now
GENERAL NOTES
JEFF SIEBEL - 02/14/2025 @ 09:08 Annual inspection $80
REINSPECTION DATE
03/12/2025
CONTACT SIGNATURE
Brian Oberheu
Signed on: 02/14/2025 @ 09:10
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/14/2025 @ 09:10