COMMERCIAL INSPECTION - 1600 OLYMPIC DR - 2-20-25
FOR BILLING INQUIRY: (319)291-4323
[Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3311
02/25/2025
03/30/2025
2025-00000281
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SUNNYSIDE COUNTRY CLUB, 1600 OLYMPIC DR, BLDG 1600 OLYMPIC DR, WATERLOO IA
S0701
DETAILS
Inspection Date: 02/20/2025 ( Inspection Type: Annual Inspection (1Yr) ( Inspection Number: 12782 Shift: N/A ( Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 49 I Violations: 7 I N/A Codes: 18
STATUS CODE DESCRIPTION
FAI L
1032.3 - Obstructions. A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
Location: Bar exit doors by banquet room
Original Comment: remove snow and ice. exit door must unlatch with less than
1 S# force and swing to full open
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Bottom of stairs to lower kitchen
Original Comment: repair exit/egress light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: from old employee break room (wine) to lower kitchen
Original Comment: repair exit light.
Printed on 02/242025 @ 08:27
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: entire building
Original Comment: Provide documentation of testing and repair of all emergency
exit and egress light with signature and date.
FAIL 603.5.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
Location: Pro shop
Original Comment: Power cord not to run thru wall cavity. Install permanent
power with permits and inspections.
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Office under Jadin's desk
Original Comment: remove extension cord . May us power strip with reset if for
computer properly supported and plugged directly into wall outlet.
Printed on 02/24/2025 @ 08:27
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERAL NOTES
JEFF SIEBEL - 02/24/2025 @ 08:22
JEFF SIEBEL - 02/24/2025 @ 08:22
JEFF SIEBEL - 02/24/2025 @ 08:23
REINSPECTION DATE
03/18/2025
CONTACT SIGNATURE
Seth Henricks
Signed on: 02/24/2025 @ 08:25
Location: Basement by old employee break room (wine) and hall
Original Comment: replace missing ceiling tile. Fire sprinkler will not function
correctly without ceililng.
annual inspection fee $100
Attic access panel replaced during inspection in pro shop
fire extingiusher due in March
Printed on 02/24/2025 @ 08:27
Page 3 of 4
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/24/2025 @ 08:25