COMMERCIAL INSPECTION - 626 SYCAMORE ST - 12-19-24
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24658
01/27/2025
02/28/2025
2025-00000249
$80.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
PRYME TYME, 626 SYCAMORE ST, BLDG 626 SYCAMORE ST, WATERLOO /A 50703
DETAILS
Inspection Date: 12/19/2024 I Inspection Type: Annual Inspec n (1Y I Inspection Numbr: 813 I Shift: NJA I Station: N/A
Unit: N/A j Lead Inspector: JEFF SIEBEL I Other Inspectors: ee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 23 ( Violations: 12 I N/A Codes: 39
STATUS CODE DESCRIPTION
FAIL 1004.9 - Posting of occupant Every room or space that is an assembly occupancy shall have the occupant load
load. of the room or space posted in a conspicuous place, near the main exit or exit
access doorway from the room or space, for the intended configurations. Posted
signs shall be of an approved legible permanent design and shall be maintained
by the owner or the owner's authorized agent.
Location: near front door
Original Comment: Post occupant load provided by fire department
Printed on 12/192024 @ 13:27
Page 1 of 6
STATUS CODE DESCRIPTION
FAI L
FAI L
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Required back exit
Original Comment: Repair or Replace fire exit with permits and inspections. Door
must unlatch and swing open with less than 15# force. Currently door will not
operate at all.
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: Ceiling
Original Comment: Repair or replace all egress lights including 3 on ceiling
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Front and Back Doors
Original Comment: Repair or replace exit lights. Lights must illuminate when
tested.
Printed on 12/19/2024 @ 13:27
Page 2 of 6
STATUS CODE DESCRIPTION
FAIL 5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Location: Entire Building
Original Comment: Provide current annual fire sprinkler inspection report with all
discrepancies corrected. Currently 338 days past due. Contractor must upload
online to the compliance engine.
FAIL 506.2 - Key box maintenance. The operator of the building shall immediately notify the fire code official and
provide the new key where a lock is changed or rekeyed. The key to such lock
shall be secured in the key box.
FAI L
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: 626 Sycamore
Original Comment: Provide current keys for bussiness in knox-box for fire fighter
access.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Back wall behind bar.
Original Comment: replace missing outlet cover
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: TV
Original Comment: remove extension cord. Power strip with manual reset may be
utilized for light duty use such as TV's, computers etc but not coolers, freezers or
heat producing devices.
Printed on 12/19/2024 @ 13:27
Page 3of6
STATUS CODE DESCRIPTION
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Front window Christmas Tree
Original Comment: Power strip with manual reset may be utilized for light duty
use such as TV's, computers etc but not coolers, freezers or heat producing
devices.
FAIL 603.8 - Temporary wiring. Temporary The use of temporary wiring for electrical power and lighting
installations shall not exceed is allowed for a period not to exceed of 90 days.
Temporary wiring methods shall meet the applicable provisions of NFPA 70.
Exception: Temporary wiring for electrical power and lighting installations is
allowed complying with the applicable provisions of NFPA 70 is permitted during
periods of construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Location: Not Provided
Original Comment: temporary lights must be removed after 90 days.
FAIL 705.2 - Inspection and Opening protectives in fire -resistance -rated assemblies shall be inspected and
maintenance. maintained in accordance with NFPA 80. Opening protectives in smoke barriers
shall be inspected and maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and maintained in accordance
with NFPA 105. Fire doors and smoke and draft control doors shall not be
blocked, obstructed, or otherwise made inoperable. Fusible links shall be
replaced promptly whenever fused or damaged. Opening protectives and smoke
and draft control doors shall not be modified.
Location: adjoining space to coridoor to restrooms and exit from 626
Original Comment: Replace missing door. Check with building official regarding
possible rating or permit requirements. Greg Ahlhelm 319-291-4319
Printed on 12/19/2024 @ 13:27
Page 4 of 6
STATUS CODE DESCRIPTION
FAIL 906.1 - Where required. Portable fire extinguishers shall be installed in all of the following locations: 1.In
new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exceptions: 1.In Group R-2 occupancies, portable fire extinguishers shall be
required only in locations specified in Items 2 through 6 where each dwelling unit
is provided with a portable fire extinguisher having a minimum rating of 1-A:10-
B:C. 2.In Group E occupancies, portable fire extinguishers shall be required only
in locations specified in Items 2 through 6 where each classroom is provided with
a portable fire extinguisher having a minimum rating of 2-A:20-B:C. 3. In storage
areas of Group S occupancies where forklift, powered industrial truck or powered
cart operators are the primary occupants, fixed extinguishers, as specified in
NFPA 10, shall not be required where in accordance with all of the following: 3.1.
Use of vehicle -mounted extinguishers shall be approved by the fire code official.
3.2. Each vehicle shall be equipped with a 10-pound, 40A:80B:C extinguisher
affixed to the vehicle using a mounting bracket approved by the extinguisher
manufacturer or the fire code official for vehicular use. 3.3. Not less than two
spare extinguishers of equal or greater rating shall be available on -site to replace
a discharged extinguisher. 3.4. Vehicle operators shall be trained in the proper
operation, use and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30 feet (9144 mm)
distance of travel from commercial cooking equipment and from domestic
cooking equipment in Group 1-1; 1-2, Condition 1; and R-2 college dormitory
occupancies. 3.In areas where flammable or combustible liquids are stored, used
or dispensed. 4.On each floor of structures under construction, except Group R-3
occupancies, in accordance with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by the fire
code official. Exception: Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where a portable fire
extinguisher suitable to the hazard of the location is provided on the vehicle of
visiting personnel.
Location: Front and back of space
Original Comment: Install 2 2A-10BC fire extinguishers 4" to 5' above the floor in
accessible locations. If purchased attach reciept to bottom of fire extinguisher.
GENERAL NOTES
JEFF SIEBEL - 12/19/2024 @ 13:26 Call Inspector if all corrections completed early.
JEFF SIEBEL - 12/19/2024 @ 13:08 annual inspection fee $80
Printed on 12/19/2024 @ 13:27
Page 5 of 6
GENERAL NOTES
JEFF SIEBEL - 12/19/2024 @ 13:10
This inspection is for 626 Sycamore only. Any use or expansion of space other than 626
Sycamore will require an architect and approval from Building Official Greg Ahlhelm
and Fire Inspector.
REINSPECTION DATE
01/16/2025
CONTACT SIGNATURE
Rodney Lewis
Signed on: 12/19/2024 @ 13:20
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 12/19/2024 @ 13:21