COMMERCIAL INSPECTION - 2134 LA PORTE RD - 1-15-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 20,000
OCCUPANCY FEE
Total Price ]
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22859
01/27/2025
02/28/2025
2025-00000240
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
FAIRFIELD INN & SUITES, 2134 LA PORTE RD, BLDG 2134 LA PORTE RD, WATERLOO /A 50702
Inspection Date: 01/15/2025 ( Inspection Type: Annual Inspection (1Yr) ( Inspection Number: 12175 ( Shift: N/A 1 Station: N/A j
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 34 I Violations: 22 I N/A Codes: 29
STATUS CODE DESCRIPTION
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: All new fire door hardware installed and additional hardware for guest
rooms
Original Comment: Obtain permit and inspections for all work planned or
completed with fire doors.
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: All new fire door hardware.
Original Comment: Provide documentation to Waterloo Building Department for
all fire door hardware when applying for permit: 1010.2.9.3 Installation. Where
panic or fire exit hardware is installed, it shall comply with the following: 1. Panic
hardware shall be listed in accordance with UL 305. 2. Fire exit hardware shall be
listed in accordance with UL 10C and UL 305.3. The actuating portion of the
releasing device shall extend not less than one-half of the door leaf width. 4. The
maximum unlatching force shall not exceed 15 pounds (67 N).
Printed on 01 /16/2025 @ 10:41
Page 1 of 9
STATUS CODE DESCRIPTION
FAIL 1103.9 - Carbon monoxide Carbon monoxide alarms detection shall be installed in existing dwelling units
alarmsdetection. and sleeping units Group 1-1, 1-2, 1-4 and R occupancies and in classrooms in
Group E occupancies where those units include any of the conditions identified in
Sections 915.1.2 through 915.1.6. The carbon monoxide alarms shall be installed
in the locations specified in Section 915.2 and the installation shall be in
accordance with Section 915.4. Exceptions: 1.Carbon monoxide alarms are
permitted to be solely battery operated where the code that was in effect at the
time of construction did not require carbon monoxide detectors to be provided.
2.Carbon monoxide alarms are permitted to be solely battery operated in
dwelling units that are not served from a commercial power source. 3.A carbon
monoxide detection system in accordance with Section 915.5 shall be an
acceptable alternative to carbon monoxide alarms.
FAIL
Location: dryer room
Original Comment: replace faulty CO detector.
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: 3rd Floor inside housekeeping by ice machine.
Original Comment: repair egress light.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: By room 407
Original Comment: Repair exit sign. unable to test battery. button missing.
Printed on 01/16/2025 @ 10:41
Page 2 of 9
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Exit sign by 308
Original Comment: repair exit sign
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required Toad for a duration of not
less than 90 minutes.
Location: Outside of pool chemical storage room
Original Comment: repair of exit light
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Pool deck
Original Comment: repair 4/5 egress lights and 2 exit lights around pool
FAIL 315.3.3 - Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms,
electrical equipment rooms or in fire command centers as specified in Section
508.1.5.
Location: All electrical and mechanical rooms
Original Comment: remove storage
Printed on 01 /16/2025 @ 10:41
Page 3 of 9
STATUS CODE DESCRIPTION
FAIL
5.2.1.1.5 - Missing
escutcheons
Escutcheons and coverplates for recessed, flush, and concealed sprinklers shall
be replaced if found missing during the inspection.
Location: Room 221
Original Comment: replace 2 missing eschutcheons
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70.2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: 3rd Floor Electrical Room
Original Comment: remove all storage. (paint included)
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: 1st floor electrical room
Original Comment: Remove storage
Printed on 01 /16/2025 @ 10:41
Page 4 of 9
STATUS CODE DESCRIPTION
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Pool chemical room
Original Comment: remove extension cord. Repair and utilize permanent outlet.
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
Location: Guest and Commercial dryer vents
Original Comment: provide documentation of dryer vent cleaning to the outside
of the building for guest dryers and housekeeping commercial dryers.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Room 433
Original Comment: replace missing smoke seal.
Printed on 01/16/2025 @ 10:41
Page 5 of 9
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
FAI L
FAI L
Location: maintenance office fire door
Original Comment: remove drop down foot. Fire door must remain closed unless
held open by a fire alarm controlled magnet.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: 4th floor East stair fire door
Original Comment: Fire door must completely self -close and latch
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: 3rd Floor East Fire Door
Original Comment: Fire door must completely self -close and latch.
Printed on 01/16/2025 @ 10:41
Page 6 of 9
STATUS CODE DESCRIPTION
FAIL 705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
FAI L
Location: Storage Room by room 401
Original Comment: Fire door must completely self -close and latch.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: 1st floor womens restroom
Original Comment: Fire door must completely self -close and latch.
FAIL 903.3.3 - Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance
with the applicable automatic sprinkler system standard that is being used.
Automatic sprinklers shall be installed in or under covered kiosks, displays,
booths, concession stands or equipment that exceeds 4 feet (1219 mm) in width.
Not less than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible fibers. Exception:
Kitchen equipment under exhaust hoods protected with a fire -extinguishing
system in accordance with Section 904.
Location: Vitality room
Original Comment: remove debris (string) from 2 fire sprinkler heads.
Printed on 01 /16/2025 @ 10:41
Page 7 of 9
STATUS CODE DESCRIPTION
FAIL 903.3.3 - Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance
with the applicable automatic sprinkler system standard that is being used.
Automatic sprinklers shall be installed in or under covered kiosks, displays,
booths, concession stands or equipment that exceeds 4 feet (1219 mm) in width.
Not less than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible fibers. Exception:
Kitchen equipment under exhaust hoods protected with a fire -extinguishing
system in accordance with Section 904.
GENERAL NOTES
JEFF SIEBEL - 01/16/2025 @ 10:27
REINSPECTION DATE
02/06/2025
Location: Room 102
Original Comment: replace fire sprinkler head . Head has paint.
Annual Inspection $100
CONTACT SIGNATURE
GM Cindy Huebner 2025
Signed on: 01/16/2025 @ 10:39
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 01/16/2025 @ 10:40
Printed on 01 /16/2025 @ 10:41