COMMERCIAL INSPECTION - 210 E TOWER PARK DR - 1-21-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 100,000
OCCUPANCY FEE
$600.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10758
01/27/2025
02/28/2025
2025-00000236
$610.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SAM'S CLUB, 210E TOWER PARK DR, BLDG 210 E TOWER PARK DR, WATERLOO M 50701
DETAILS
Inspection Date: 01/21/2025 ( Inspection Type: Annual Inspection (1Yr) ; Inspection Number: 12174 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: JEREMIAH VANDYKE
910
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 51 I Violations: 6 I N/A Codes: 16
STATUS CODE DESCRIPTION
FAI L
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: Exit door by eco lab # 7 and case of shell oil
Original Comment: Repair exit door. Exit door must unlatch and swing to full
open with less than 15# force. Door would not open at all today. If replaced
obtain permits and inspectcions.
Printed on 01/22/2025 @ 09:58
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: Provide documentation of testing and repair of all emergency exit and
egress lights with signature and date.
FAIL 315.3.1 - Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in
nonsprinklered areas of buildings or not less than 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings. Exceptions: 1.The 2-
foot (610 mm) ceiling clearance is not required for storage along walls in
nonsprinklered areas of buildings. 2.The 18-inch (457 mm) ceiling clearance is not
required for storage along walls in areas of buildings equipped with an automatic
sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
FAIL
FAI L
Location: Aisle by fire door by ecolab #7 and Shell Oil Case
Original Comment: Lower storage to allowable height. Currently almost touching
plastic and would hold it up.
5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: Annual Fire Sprinkler Inspection Deficiencies -dry heads need testing
Original Comment: Provide current annual fire sprinkler sprinker inspection
report with all deficiencies corrected. Current report lists 2 deficiencies.
Contractor must upload corrections online to the compliance engine.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Cash room
Original Comment: install missing outlet cover.
Printed on 01/22/2025 @ 09:58
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: Cash room and fire pump room
Original Comment: remove portable electric heaters or provide documentation
of listing of use for commerial use and proper clearances.
GENERAL NOTES
JEFF SIEBEL-01/22/2025 @ 08:20 annual inspection $600
JEFF SIEBEL - 01/22/2025 @ 09:53 Fire door drop test 5/13/24
JEFF SIEBEL - 01/22/2025 @ 09:53 Fire pump maintenance Elite 2/20/24
JEFF SIEBEL - 01/22/2025 @ 09:54 Fire Alarm inspection due 3/19/25
JEFF SIEBEL - 01/22/2025 @ 09:54 hood fire suppression due 3/30/25
REINSPECTION DATE
02/11/2025
CONTACT SIGNATURE
Mike Ahmann - Fresh Manager
Signed on: 01/22/2025 @ 09:55
Printed on 01/22/2025 @ 09:58