COMMERCIAL INSPECTION - 218 DIVISION ST - 12-19-24
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE.
DUE DATE
INVOICE #
CHARGES
5729
01/27/2025
02/28/2025
2025-00000248
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
CEDAR VALLEY FISH MARKET, 218 DIVISION ST, BLDG 218 DIVISION ST, WATERLOO IA 50703
Inspection Date: 12/19/2024 I Inspection Type: Annual Inspe ion ( r) I Inspection Numbe\: 11502 j Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: /A Fee: $80.00
VIOLATIONS ANO COMPLIANCES
Showing only violations and images for this inspection.lease reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 30 I Violations: 4 I N/A Codes: 40
STATUS CODE
FAI L
FAI L
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
DESCRIPTION
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Basement
Original Comment: remove 2 freezers from power strip. They must plug directly
into permanent wall outlet.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Front of store
Original Comment: remove multiplug adapter from adding machine and price
display. Power strip with manual reset may be utilized for light duty items such as
computers, tv's etec but for nothing with a motor or anything that produces
heating or cooling.
Printed on 12/19/2024 @ 14:31
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood fire suppression inspection report
Original Comment: Provide current kitchen hood fire suppression inspection
report with all discrepancies corrected. Currently 6 days past due. Contractor
must upload online to the compliance engine.
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: upstairs and downstairs
Original Comment: Provide annual service for fire extingiusers.
GENERAL NOTES
JEFF SIEBEL - 12/19/2024 @ 14:28 annual inspection $80
REINSPECTION DATE
01/23/2025
Printed on 12/19/2024 @ 14:31
Page2of3
CONTACT SIGNATURE
Noel Morris Jr. or JR
Signed on: 12/19/2024 @ 14:27
a-wrv: /
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 12/19/2024 @ 14:27