COMMERCIAL INSPECTION - 209 W 5TH - 5-9-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
4749
06/11/2025
07/15/2025
2025-00000389
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
---
Waterloo Fire R
spection Report
Russell -Lamson - 209 W 5th ST, BLDG 209 W. 5th,St, Waterloo IA 50702
INSPECTION • - a LS
Inspection Date
05/09/2025
Inspection Type
Residential Common Areas Inspection
425 E. 3rd Street
Inspection Number
13743
Lead Inspector Shift Station Unit
JEREMIAH VANDYKE N/A NIA NIA
Other Inspectors
BROCK WELIVER
SUMMARY OF INSPECTION
0 22
Passed codes
NEXT STEPS
0 15
Failed codes
5
N/A codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
FEE
Invoice Date Inspection Fee
N/A
Date Paid Amount Paid
Reinspection Date
06/0812025
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERAL NOTES
JEREMIAH VANDYKE - 05/09/2025 @ 16:34
Last Dryer cleaned 4130/2024. Cleaned in House by Mark.
JEREMIAH VANDYKE - 05109/2025 @ 16:35
Fire extinguishers serviced by Superior Dec. 2024.
JEREMIAH VANDYKE - 05/09/2025 @ 16:58
Last recorded in house boiler log checkoff completed by Justin 5/8/2025. System was at 40 PSI.
JEREMIAH VANDYKE - 05/09/2025 @ 17:41
Discussed with Justin on getting logs for boilers, generator, EXIT/Egress lighting, and clothes dryer recorded and logged correctly. Discussed with Justin
on talking to the contractors on how to properly maintain equipment and how to log correctly.
JEREMIAH VANDYKE - 05109/2025 @ 17:40
PERMIT INFO: a€6 Any construction requires proper permit and inspections. 9€6 All electrical work and repair must be completed by a licensed electrical
contractor with permits and inspections.
JEREMIAH VANDYKE - 05/09/2025 @ 17:41
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday a€" Friday, 8:00 a.m. A€" 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be
performed the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. *****Re
inspection fees may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 05109/2025 @ 17:41
GENERATED ON 5/9/25, 12:44 PM 1 OF 5
r
Lt. Van Dyke_- emiah.vandyke@waterloo-ia.oTg-at" Work: 319-291-4460 - CeII: 319-883-1615
JEREMIAH VANDYKE - 05/09/2025 @ 17:41
Inspection Fee = $100.00 (To be mailed out by City via snail mail.) )
JEREMIAH VANDYKE - 0510912025 @ 17:39
7/12/2024 S - (Annual) Standpipe BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed Compliant
JEREMIAH VANDYKE - 05/09/2025 @ 17:39
7/12/2024 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed Compliant
JEREMIAH VANDYKE - 0510912025 @ 17:40
7/12/2024 S - (Annual) Fire Pump BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed Deficient Compliant
JEREMIAH VANDYKE - 05/0912025 @ 17:40
6/25/2024 S - (Annual) Fire Alarm HAWKEYE ALARM Reviewed Compliant
SIGNATURES
Contact signature Inspector signature
No signature
NA
Kathy Nelson
CHECKLISTS
Residential Common Areas Inspection
.L/f
Date: JEREMIAH VANDYKE 05/09/2025
Status Code Description
Fail 1032.4
0 Exit signs shall be installed and maintained in accordance Location: Near Crestroom in Lobby area.
with the building code that was in effect at the time of Comments: Exit/egress Tight tested and failed. Need to replace or
construction and the applicable provisions in Section 1104. repair.
Decorations, furnishings, equipment or adjacent signage that
impairs the visibility of exit signs, creates confusion or
prevents identification of the exit shall not be allowed.
Fail
Fail
1032.4
Exit signs shall be installed and maintained in accordance
with the building code that was in effect at the time of
construction and the applicable provisions in Section 1104.
Decorations, furnishings, equipment or adjacent signage that
impairs the visibility of exit signs, creates confusion or
prevents identification of the exit shall not be allowed.
1104.5
Where means of egress illumination is provided, the power
supply for means of egress illumination shall normally be
provided by the premises&€'" electrical supply. In the event
of power supply failure, illumination shall be automatically
provided from an emergency system for the following
occupancies where such occupancies require two or more
means of egress: 1.Group A having 50 or more occupants.
Location: In basement near elevator B Hallway.
Comments: Exit light is hanging and needs repaired.
Location: Stairway near boiler room on 2nd level going to first level.
Comments: Egress lights on walls are burned out and need repaired
or replaced.
GENERATED ON 5/9/25, 12:44 PM 2 OF 5
Fail
Exception: Assembly occupancies used exclusively as a
place of worship and having an occupant Toad of less than
300. 2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants. 3.Group E in interior exit
access and exit stairways and ramps, corridors, windowless
areas with student occupancy, shops and laboratories.
4.Group F having more than 100 occupants. Exception:
Buildings used only during daylight hours and that are
provided with windows for natural light in accordance with
the International Building Code . 5.Group I. 6.Group M.
Exception: Buildings less than 3,000 square feet (279 m2) in
gross sales area on one story only, excluding mezzanines.
7.Group R-1. Exception: Where each sleeping unit has direct
access to the outside of the building at grade. 8.Group R-2.
Exception: Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
1104.5
0 Where means of egress illumination is provided, the power
supply for means of egress illumination shall normally be
provided by the premisesiz€'' electrical supply. In the event
of power supply failure, illumination shall be automatically
provided from an emergency system for the following
occupancies where such occupancies require two or more
means of egress: 1.Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a
place of worship and having an occupant Toad of less than
300. 2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants. 3.Group E in interior exit
access and exit stairways and ramps, corridors, windowless
areas with student occupancy, shops and laboratories.
4.Group F having more than 100 occupants. Exception:
Buildings used only during daylight hours and that are
provided with windows for natural light in accordance with
the International Building Code . 5.Group I. 6.Group M.
Exception: Buildings less than 3,000 square feet (279 m2) in
gross sales area on one story only, excluding mezzanines.
7.Group R-1. Exception: Where each sleeping unit has direct
access to the outside of the building at grade. 8.Group R-2.
Exception: Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
Fail
Fail
Fail
2015 IFC
Is the fire alarm system powered, operational and displaying
normal operation (no troubles, supervisory, or alarms)?
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
Location: Vacant Corner suite on 1st floor.
Comments: Egress Tight near kitchen tested and failed. Need to repair
or replace.
Location: Basement in Main electrical room.
Comments: NAC unit is has trouble signal, but not reporting to main
panel on 1st floor. Need to contact fire alarm contractor to address.
Location: Smaller far west generator.
Comments: Alarm mode light is flashing red. Need generator
contractor to address issue. Also generator is filled with pigeon
feces.
Location: Stairwell B all fire doors on all floors.
Comments: Painted over fire rated tags. Will need to remove paint.
GENERATED ON 5/9/25, 12:44 PM 3 OF 5
Fail
l^J
Fad
Fail
O
Fail
Fail
O
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
901.6
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
Additional Codes
Status
Fail
Code
5.2.1.1.5
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Location: Both Generators.
Comments: Annual maintenance report needed for both generators
from Generator contractor.
Location: In house generator log.
Comments: Discussed with Justin on getting monthly maintenance
log and learning from Generator contractors on tracking hours and
maintenace for generators.
Location: Fire pump monthly testing.
Comments: Black Hawk sprinkler is doing monthly testing on fire
pump. Need a mainteance log or invoices of the testing being
completed.
Location: Boiler inspection reports.
Comments: Need last completed inspection report completed by
boiler contractor.
Location: Generator panels on 1st floor near Main fire alarm panel.
Comments: Need to have Generator contractor address both
generator panels on 1st floor. One has no lights and looks out of
service. The other panel did not pick up the Alarm mode on far west
generator.
Description
Location: Suite 1 first floor.
Comments: Missing eschutcheon plate in hallway area. Need to
replace.
GENERATED ON 5/9/25, 12:44 PM 4 OF 5
Fail
Fail
5003.4
Safety Data Sheets (SDS) shall be readily available on the
premises for hazardous materials regulated by this chapter.
Where a hazardous substance is developed in a laboratory,
available information shall be documented. Exception:
Designated hazardous waste.
603.2
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Location: Basement SDS yellow book.
Comments: SDS book in basement has no paperwork in it for
chemicals on property. Please get the appropriate paperwork for
chemicals on site into the SDS book in the basement.
Location: Outside main entrance office area missing Tamp.
Comments: Exposed wiring needs to be covered until lamp is fixed.
GENERATED ON 5/9/25, 12:44 PM