COMMERCIAL INSPECTION - 1340 LOGAN AVE - 12-19-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
7692
12/19/2025
01/22/2026
2026-00000272
$100.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Dollar Tree - 1340 Logan AVE, BLDG 1340 Logan Ave, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
12/19/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr) REINSPECTION )
other Inspectors
NIA
Shift
NIA
425 E. 3rd Street
Inspection Number
2586-R2
Station Unit
N/A NIA
SUMMARY OF INSPECTION
Oo
Passed codes
NEXT STEPS
7
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 11/20/2025 @ 13:57
$80 annual inspection fee
BRAD BALDWIN - 11/2012025 @ 13:57
Fire extinguishers due annually serviced in March 2026
Reinspection Date
0111612026
BRAD BALDWIN - 11120/2025 @ 13:57
Noted east exterior vent discharge caps missing. Suggesting proper covers to be installed to avoid bird nesting blocking vents. Not a fire code violations.
BRAD BALDWIN - 11120/2025 @ 13:57
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
GENERATED ON 12/19/25, 2:32 PM 1 OF 6
BRAD BALDWIN - 11/20/2025 @ 13:57
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 12/19/2025 @ 14:20
$100 re -inspection fee, failure to complete corrections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Shane Lawton (2025) local
CHECKLISTS
Date: BRAD BALDWIN 12/19/2025
GENERATED ON 12/19/25, 2:32 PM
2 OF 6
Reinspection
Status Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Description
Location: Water heater
Comments: Licensed plumbing contractor shall obtain plumbing
permit and inspection of water heater installed without permit.
Additional comments: No progress made today.
Location: Back storage gas heater
Comments: Licensed contractor shall obtain proper permits and
inspection of heater installed without permits. Mike Fereday sticker
noted on heater.
Additional comments: No progress made today
GENERATED ON 12/19/25, 2:32 PM
3 OF 6
Fail
o
Fail
0
Fail
0
Fail
Q
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Location: Back storage area
Comments: Remove all obstructions to clear path of access to exit
door. Maintain clear path at all times.
Additional comments: Picture attached from today's inspection
12/19/25. Remove all obstructions in exit path.
Location: Emergency egress lights
Comments: Provide documentation of testing and repairs completed
report of all egress lighting in building. Report to include name of
person testing and date of completion, report may be emailed to
inspector. Back room near bathrooms light failed today.
Location: Exit signs
Comments: Provide documentation of testing and repairs completed
report of all exit signage in building. Report to include name of
person testing and date of completion, report may be emailed to
inspector.
Comments: Provide permanent sign on door to electric panels area,
laminated paper will not be accepted. Sign to be red in color with
white lettering.
GENERATED ON 12/19/25, 2:32 PM 4 OF 6
Additional Codes
Status
Fail
F�
Code
603.9.4 - Prohibited areas.
Portable, electric space heaters shall not be operated within 3
feet (914 mm) of any combustible materials. Portable, electric
space heaters shall be operated only in locations for which
they are listed.
Description
Location: Register area
Comments: Provide documentation of proper label and listing of use
in commercial space or remove from building.
GENERATED ON 12/19/25, 2:32 PM
5 OF 6