COMMERCIAL INSPECTION - 1215 ANSBOROUGH AVE - 1-2-26
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 3
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23975
01/02/2026
02/03/2026
2026-00000283
$200.00
Less Prepayment
Total Due -->
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
�,,.•, Waterloo Fire Rescue
Inspection Report
Burger King - 1215 Ansborough AVE, BLDG 1215 Anborough Ave, Waterloo IA 50701
INSPECTION DETAILS
425 E. 3rd Street
Inspection Date Inspection Type Inspection Number
0110212026 Annual Inspection (1Yr) REINSPECTION ) 17230-R6
Lead Inspector
BRAD BALDWIN
Other inspectors
NIA
Station
N/A NIA
Lind
NIA
SUMMARY OF INSPECTION
0 Q
Passed codes
NEXT STEPS
0 5
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 12/03/2025 @ 14:52
$100 re -inspection fee, failure to correct violations.
BRAD BALDWIN - 12/03/2025 @ 14:52
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
01/30/2026
BRAD BALDWIN - 12/03/2025 @ 14:52
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 12/03/2025 @ 14:52
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *"***Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 12/03/2025 @ 14:52
$80 annual inspection fee
BRAD BALDWIN - 12/03/2025 @ 14:52
No re -inspection fee today 8/13/25, progress made on corrections.
BRAD BALDWIN - 12/03/2025 @ 14:52
$150 re -inspection fee, failure to correct violations. Complete corrections to avoid reoccurring inspection fees.
BRAD BALDWIN - 12/03/2025 @ 14:52
$200 re -inspection fee, failure to correct violations, fees will continue till violations are corrected. Left voicemail for District Manager (Star Patillo)
10/31/25, do not have contact information to email reports to her.
BRAD BALDWIN - 12/03/2025 @ 14:52
GENERATED ON 1/2/26, 2:46 PM 1 OF 5
$200 re -inspection fee, continuing to fail to complete corrections. Fees will continue till violations are corrected. Please contact inspector with any
questions regarding report.
BRAD BALDWIN - 01/02/2026 @ 14:44
$200 re -inspection fee, failure to complete corrections as of 112/26.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
313
Daytoviane McLemore (2025) Date: BRAD BALDWIN 01/02/2026
CHECKLISTS
GENERATED ON 1/2/26, 2:46 PM
2 OF 5
Reinspection
Status Code
Fail 1032.2 - Reliability.
0 Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Fail
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSI/IKECA C10.
Description
Location: Kitchen exit
Comments: Pile of boxes noted in egress exit path today. Remove all
obstructions to exit path and maintain clear path at all times.
Additional comments: Boxes still in exit path today 1/2126.
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine.
Additional comments: No progress made today - 112126
Location: Kitchen hood exhaust
Comments: Clean hood exhaust and suppression system piping,
noted significant accumulation of grease as shown in picture taken
10/31/25.
Additional comments: "All Seasons" tagged hood cleaning
completed in December 2025. Contractor shall upload report to
Compliance Engine with deficiencies corrected.
GENERATED ON 1/2/26, 2:46 PM
3 OF 5
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.4.2 - Class K portable fire extinguishers for deep fat
fryers.
Where hazard areas include deep fat fryers, listed Class K
portable fire extinguishers shall be provided as follows: 1.For
up to four fryers having a maximum cooking medium capacity
of 80 pounds (36.3 kg) each: one Class K portable fire
extinguisher of a minimum 1.5-gallon (6 L) capacity. 2.For
every additional group of four fryers having a maximum
cooking medium capacity of 80 pounds (36.3 kg) each: one
additional Class K portable fire extinguisher of a minimum
1.5-gallon (6 L) capacity shall be provided. 3.For individual
fryers exceeding 6 square feet (0.55 m2) in surface area:
Class K portable fire extinguishers shall be installed in
accordance with the extinguisher manufacturer's
recommendations.
Location: All fire extinguishers
Comments: Provide annual service to fire extinguishers. Past due as
of Feb 2025
Additional comments: No progress made today - 112126
FIRE a SAFETY LLG
636-812-2183
MOM t
i ICFNSE N6. Si. Louie City Y I9
SERVICED BY:>
Location: Kitchen class K extinguisher
Comments: Provide annual service to extinguisher.
Additional comments: No progress made today - 112/26
GENERATED ON 1/2/26, 2:46 PM