HomeMy WebLinkAbout1915 BOURLANDINVOICE DATE
DUE DATE,
INVOICE #
TOTAL DUE
12/09/2025
01/10/2026
2026-00000254
$80.00
Customer #: 23343
FUSION BAR
1915 BOURLAND
WATERLOO, IA 50702
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1915 BOURLAND-11-17-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23343
12/09/2025
01/10/2026
2026-00000254
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Fusion Bar - 1915 Bourland AVE, BLDG 1915 Bourland Ave, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
11/17/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other inspectors
N/A
3(--i3
425 E. 3rd Street
Inspection Number
15262
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 38
Passed codes
NEXT STEPS
0 11
Failed codes
29
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 11/18/2025 @ 07:43
$80 annual inspection fee
BRAD BALDWIN - 11/1812025 @ 07:45
Fire extinguishers self -purchased (11/5125). Receipt taped to bottom.
Reinspection Date
12/10/2025
BRAD BALDWIN - 11/18/2025 @ 07:55
Corrected during 11/17125 inspection: (1) Removed light cord running through doorway from kitchen to hallway. (2) Removed extension cord behind
kitchen fridge.
BRAD BALDWIN - 11118/2025 @ 08:11
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
BRAD BALDWIN - 11/18/2025 @ 08:11
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 11/18/2025 @ 08:11
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100. then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 11/18/25, 8:33 AM 1 OF 8
Hassan Puric
CHECKLISTS
Emergency Equipment
States Code
Fail
Fail
Date:
BRAD BALDWIN 11/1812025
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Storage room
Comments: Repair or replace egress lights that failed to illuminate
during test.
Location: East exit
Comments: Repair or replace exit sign & lights that failed to
illuminate during test.
GENERATED ON 11/18/25, 8:33 AM 2 OF 8
Electrical Safety
Status Code
Fail
603.4 - Working space and clearancesciearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Storage room
Comments: Clear obstructions to clear path of access to electric
panels. Maintain path at all times.
GENERATED ON 11/18/25, 8:33 AM
3 OF 8
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Fail 603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Location: Seating area
Comments: Properly mount power strip to wall or support on shelf
avoid hanging by wires.
Location: Storage room near electric panels
Comments: Properly mount power strip to wall or support on shelf
avoid hanging by wires.
GENERATED ON 11/18/25, 8:33 AM 4 OF 8
Fail
C.
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Seating area
Comments: Remove white extension cord and lighting cord from
above drop ceiling. Flexible cords not allowed in concealed areas.
Location: Jukebox
Comments: Remove jukebox from multi -plug extension cord. May
replace with power strip with manual reset plugged directly to wall
outlet or licensed electrical contractor may add outlet with permit and
inspection.
GENERATED ON 11/18/25, 8:33 AM 5 OF 8
Fail
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.8 - Temporary wiring.
Temporary The use of temporary wiring for electrical power
and lighting installations shall not exceed is allowed for a
period not to exceed of 90 days. Temporary wiring methods
shall meet the applicable provisions of NFPA 70. Exception:
Temporary wiring for electrical power and lighting
installations is allowed complying with the applicable
provisions of NFPA 70 is permitted during periods of
construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Location: Above bar beverage fridge
Comments: Remove orange extension cord from permanent usage.
Allowed for temporary use only for light duty electric.
Location: Above pool table
Comments: Remove white cord and also Budweiser cord from above
drop ceiling. Flexible cords not allowed in concealed areas.
Location: Exterior Christmas lighting
Comments: Lighting allowed for 90 days, shall be removed by
2/15/25.
GENERATED ON 11/18/25, 8:33 AM 6 OF 8
Additional Codes
Status Code
Fail
807.2 - Combustible decorative materials.
In Groups A, B, E, I, M and R-1 and in dormitories in Group R-
2, curtains, draperies, fabric hangings and other similar
combustible decorative materials suspended from walls or
ceilings shall comply with Section 807.3 and shall not exceed
10 percent of the specific wall or ceiling area to which such
materials are attached. Fixed or movable walls and partitions,
paneling, wall pads and crash pads applied structurally or for
decoration, acoustical correction, surface insulation or other
purposes shall be considered to be interior finish, shall
comply with Section 803 and shall not be considered
decorative materials or furnishings. Exceptions: 1.In
auditoriums in Group A, the permissible amount of curtains,
draperies, fabric hangings and similar combustible decorative
material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1, and where the
material is installed in accordance with Section 803.15 of the
International Building Code. 2.In Group R-2 dormitories,
within sleeping units and dwelling units, the permissible
amount of curtains, draperies, fabric hangings and similar
decorative materials suspended from walls or ceilings shall
not exceed 50 percent of the aggregate wall areas where the
building is equipped throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.
3.In Group B and M occupancies, the amount of combustible
fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 807.3 and
shall not be limited. 4.The 10-percent limit shall not apply to
curtains, draperies, fabric hangings and similar combustible
decorative materials used as window coverings.
Description
Location: Kitchen
Comments: Window coverings shall be removed or replaced with
proper fire -retardant material.
GENERATED ON 11/18/25, 8:33 AM 7 OF 8
Statement of Fees
FEE
invoice Date Inspection Fee
NIA $80.00
Date Paid Amount Paid
Invoice Number
NIA
Check Number
NIA
Transaction Number
N/A