COMMERCIAL INSPECTION - 325 COMMERCIAL - 11-21-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22975
12/09/2025
01/10/2026
2026-00000248
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Single Speed Brewing - 325 Commercial ST, BLDG 325 Commercial St, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
11/21/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Qiac1.-7s
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
15713
Shit, Station Unit
N/A N/A N/A
SUMMARY OF INSPECTION
0 56
Passed codes
NEXT STEPS
11
Failed codes
10
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 11/2412025 @ 13:19
$100 annual inspection fee
BRAD BALDWIN - 11/24/2025 @ 13:35
Kitchen exhaust hood suppression system due for service 1-9-26
BRAD BALDWIN - 11/24/2025 @ 13:39
Fire extinguishers due annually serviced in May 2026
Reinspection Date
12/18/2025
BRAD BALDWIN - 11124/2025 @ 13:47
Corrected during 11/21/25 inspection: (1) Removed cart blocking kitchen hood suppression pull station and fire extinguisher. (2) Removed item resting on
sprinkler pipe in kitchen.
BRAD BALDWIN - 11/24/2025 @ 13:54
Contractor permits obtained for current remodel shall be inspected and passed at time of completion of work.
BRAD BALDWIN - 1112412025 @ 13:54
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 11/24/2025 @ 13:54
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 11/24/2025 @ 13:54
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 11/24/2025 @ 13:57
GENERATED ON 11/24/25, 2:00 PM
1 OF 9
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Derrick Akers Date: BRAD BALDWIN 1112412025
CHECKLISTS
Means of Egress
cod, Description
Fail 1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Code
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail 1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Boiler room
Comments: Remove obstructions to exit path (floor scrubber, boxes,
chair). Maintain clear path to exit at all times.
Description
Comments: Provide report of testing of all emergency egress lighting
including repairs made with signature and date. Email report to
inspector.
Comments: Provide report of testing of all exit signs including
repairs made with signature and date. Email report to inspector.
GENERATED ON 11/24/25, 2:00 PM
2 OF 9
Additional Codes
Coda
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Description
Location: Walk-in beer cooler
Comments: Secure compressed beer gas tanks with chain to avoid
tip over.
GENERATED ON 11/24/25, 2:00 PM 3 OF 9
Fail 5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Location: Brewery lab
Comments: Secure compressed gas cylinder with chain to avoid tip
over.
Location: Bar mini fridges (2)
Comments: Fridges plugged to power strips shall be plugged directly
to wall outlets. Relocate fridges or licensed electrical contractor may
add outlet with obtaining permit and inspection.
GENERATED ON 11/24/25, 2:00 PM
4 OF 9
Electrical Safety
Status cod:*
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
sciption
Location: Water Tank Room (Panel LVIC)
Comments: Remove pallets and all storage within 36" in front of
panels. Maintain clearances at all times.
GENERATED ON 11/24/25, 2:00 PM
5 OF 9
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Outside office
Comments: Remove combustibles (plastic) and all storage from
within 36" of electric panels. Maintain clearance at all times.
GENERATED ON 11/24/25, 2:00 PM
6 OF 9
Fail
Fail
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Location: Bar
Comments: Remove cube style multi -plug adapter. May replace with
properly mounted power strip with manual reset for Tight duty electric
only.
Location: Bar, near mini fridges
Comments: Power strip shall be properly supported or mounted on
wall to avoid hanging by wires
GENERATED ON 11/24/25, 2:00 PM
7 OF 9
Commercial Cooking Hood Suppression System
Sttu_ Cai_
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
Description
Location: Kitchen exhaust hood
Comments: Exhaust system cleaning past due as of 11/21125. Provide
cleaning and report to be uploaded to Compliance Engine with any
deficiencies corrected.
GENERATED ON 11/24/25, 2:00 PM
8 OF 9