COMMERCIAL INSPECTION - 306 WASHINGTON ST - 11-24-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
21386
12/09/2025
01/10/2026
2026-00000246
$80.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Snowden House - 306 Washington ST, BLDG 306 Washington St, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
11/24/2025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
15873
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
029 08 ®37
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 11125/2025 @ 08:53
$80 annual inspection fee
BRAD BALDWIN - 11125/2025 @ 09:34
Corrected during 11/24/25 inspection: Removed power strip from extension cord on stage 2nd floor.
BRAD BALDWIN - 11125/2025 @ 13:47
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
12118/2025
BRAD BALDWIN - 11/25/2025 @ 13:47
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 11125/2025 @ 13:47
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
Alan Sweeney
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 11/25/2025
GENERATED ON 11/25/25, 1:50 PM 1 OF 6
Means of Egress
Status Code
Fail
1104.16.5.1 - Examination.
Fire escape stairways and balconies shall be examined for
structural adequacy and safety in accordance with Section
1104.16.5 by a registered design professional or others
acceptable to the fire code official every 5 years, or as
required by the fire code official. An inspection report shall be
submitted to the fire code official after such examination.
Emergency Equipment
status Code
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Status Code
Fail
305.1- Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Additional Codes
Status Code
Fail
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Fire escape
Comments: Provide 5 year inspection report by licensed contractor.
Email report to inspector.
Description
Comments: Provide report with any deficiencies corrected of all
emergency egress lighting in building with date and signature of
person testing. Email report to inspector.
Comments: Provide report with any deficiencies corrected of all exit
signs in building with date and signature of person testing. Email
report to inspector.
Description
Location: Basement
Comments: Remove combustible material from within 36" from gas
fired appliances. Maintain clearance at all times.
Description
Location: Basement
Comments: Remove dehumidifier from extension cord, shall be
plugged directly to wall outlet. Extension cord for temporary use
only.
GENERATED ON 11/25/25, 1:50 PM 2 OF 6
Electrical Safety
£ifiE;;S Code
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: West exterior of building behind A/C's
Comments: Repair box to avoid hanging by wires.
GENERATED ON 11/25/25, 1:50 PM
3 OF 6
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: 2nd floor stage
Comments: Remove storage within 36 " in front of electric panel.
Maintain clearance at all times.
GENERATED ON 11/25/25, 1:50 PM
4 OF 6
Portable Fire Extingusihers
Scat€.= Cod;:
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.1.-oss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to all fire extinguishers, currently
past due as of October 2025