COMMERCIAL INSPECTION - 5-9 NORTH ELK RUN RD-11/04/2025
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 1
OCCUPANCY FEE
Total Price
$40.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24844
11/14/2025
12/19/2025
2026-00000194
$50.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$50.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Bringing the Chi Bar & Grill. - 5-9 N Elk Run RD, BLDG 5 N Elk Run Rd, Waterloo IA
50703
INSPECTION DETAILS
#z^:s taat €:,n Date
11104/2025
Lend Inspectnt
JEREMIAH VANDYKE
Inspection Type
Annual Inspection (1Yr)
Otherinspectors
NIA
Inspection Number
13956
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
38
Passed codes
NEXT STEPS
Failed codes
Q 28
NIA codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 11/0412025 @ 11:20
Fire extinguishers serviced by Proshield October 2025.
Reinspection Date
11/1812025
JEREMIAH VANDYKE - 11/04/2025 @ 11:20
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday - Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be performed
the following Monday or Tuesday. It all corrections are made before the 30 days, you can call to set up an earlier re -inspection. *****Re inspection fees
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 11/0412025 @ 11:21
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 11/04/2025 @ 11:21
Inspection Fee = $50.00 (To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Anton Garrett
CHECKLISTS
GENFRATED ON 11/4/25, 11.22 AM
Date:
JEREMIAH VANDYKE 11/04/2025
1 OF 5
Means of Egress
` aw fix
Fail
Fail
Coo :
1004.9 - Posting of occupant Toad.
Every room or space that is an assembly occupancy shall
have the occupant load of the room or space posted in a
conspicuous place, near the main exit or exit access doorway
from the room or space, for the intended configurations.
Posted signs shall be of an approved legible permanent
design and shall be maintained by the owner or the owner's
authorized agent.
1010.2.5 - Bolt locks.
Manually operated flush bolts or surface bolts are not
permitted. Exceptions: 1.0n doors not required for egress in
individual dwelling units or sleeping units. 2.Where a pair of
doors serves a storage or equipment room, manually
operated edge- or surface -mounted bolts are permitted on the
inactive leaf. 3.Where a pair of doors serves an occupant load
of less than 50 persons in a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are
permitted on the inactive leaf. The inactive leaf shall not
contain doorknobs, panic bars or similar operating hardware.
4.Where a pair of doors serves a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are
permitted on the inactive leaf provided that such inactive leaf
is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1. The inactive leaf
shall not contain doorknobs, panic bars or similar operating
hardware. 5.Where a pair of doors serves patient care rooms
in Group 1-2 occupancies, self -latching edge- or surface -
mounted bolts are permitted on the inactive leaf provided that
the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain
doorknobs, panic bars or similar operating hardware.
Emergency Equipment
Status
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Need updated occupant load sign. I will drop off on
reinspect.
Comments: Need updated occupant load sign. I will drop off on
reinspect.
Location: East door leading out from public area.
Comments: Door has 2 locks. Discussed keeping the thumb turn and
removing lock from door handle mechanism.
Description
Location: Back hallway storage area exit sign.
Comments: Discussed covering the "Exit" part of sign with paper
since it is not a required exit.
GENERATED ON 11/4/25, 11:22 AM
2 OF 5
General Housekeeping
Status
FailF��
Code
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Commercial Cooking Hood Suppression System
Slaiuv Code
Fail
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.3 - Records.
Records for inspections shall state the individual and
company performing the inspection, a description of the
inspection and when the inspection took place. Records for
cleanings shall state the individual and company performing
the cleaning and when the cleaning took place. Such records
shall be completed after each inspection or cleaning and
maintained.
Location: UL listed oily rag container is needed for the kitchen.
Comments: Picture of example below. Please contact me if you have
any questions.
Description
Location: Nozzle location for appliances.
Comments: After cooking appliances are placed contact Proshield to
adjust nozzles for proper spray coverage.
Location: Hood Cleaning and hood suppression report needs to be
uploaded to compliance engine by contractor.
Comments: I contacted Proshield and they will be getting the report
uploaded.
GENERATED ON 11/4/25, 11:22 AM 3 OF 5
Portable Fire Extingusihers
Status Code.
Fail
x
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Red commercial fire extinguisher needs to be mounted in
kitchen by silver class K extinguisher.
Comments: Red commercial fire extinguisher needs to be mounted in
kitchen by silver class K extinguisher.