COMMERCIAL INSPECTION - 814 LAPORTE RD-10/16/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 1
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24834
11/14/2025
12/19/2025
2026-00000203
$100.00
Less Prepayment
Total Due
City of Waterloo
$0.00
S100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Dallas Fresh - 814 La Porte RD, BLDG 814 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection D64,
10/16/2025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
REINSPECTION
Other Inspectors
N/A
Shift
N/A
425 E. 3rd Street
Inspection Number
11796-R2
Station Unit
N/A N/A
SUMMARY OF INSPECTION
0 0 2
Passed codes Resolved violations
NEXT STEPS
08
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/2512025 @ 15:17
$80 annual inspection fee
BRAD BALDWIN - 09/2512025 @ 15:17
Fire extinguishers due annually serviced by January 2026
BRAD BALDWIN - 09/25/2025 @ 15:17
Specific questions regarding electrical requirements shall be directed to Electrical Inspector, Tim Moyer at 319-464-5683.
BRAD BALDWIN - 09125/2025 @ 15:17
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09/25/2025 @ 15:17
Reinspection Date
11110/2025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 09/25/2025 @ 15:17
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 09/25/2025 @ 15:17
Withholding re -inspection today 9/25/25 due to significant progress made. Provide record of electrical work completed by licensed electrical contractor.
BRAD BALDWIN - 10/16/2025 @ 15:32
$100 re -inspection fee, failure to correct violations
BRAD BALDWIN - 10/16/2025 @ 15:41
Per City Clerk's Office: Liquor license invalid as of 10116/25, alcohol shall be removed from building without valid liquor license.
GENERATED ON 10/17/25, 8:19 AM 1 OF 8
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
EES
ALBERTO BALTIERRA Date: BRAD BALDWIN 10117/2025
CHECKLISTS
GENERATED ON 10/17/25, 8:19 AM 2 OF 8
Reinspection
Status Code
Fail
0
Fail
0
Fail
601.2 - Hazard abatement.
Operations or conditions deemed unsafe or hazardous by the
fire code official shall be abated. Equipment, appliances,
materials and systems that are modified or damaged and
constitute an electrical shock or fire hazard shall not be used.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Walk in fridge
Comments: Cord unprotected from sharp metal edge should be
corrected to avoid shock hazard. Appliance cord and or plug end
altered, licensed electrical contractor shall inspect, repair or replace.
Copy of receipt of work completed shall be kept to show inspector.
Additional comments: No progress today
Location: Hallway to mechanical room light fixtures
Comments: Light fixture wiring shall be inspected by licensed
electrical contractor, repaired or replaced . Copy of receipt of work
completed shall be kept to show inspector.
Additional comments: No progress today
Location: Beverage fridge in front of bar
Comments: Appliance cord and or plug end altered, licensed
electrical contractor shall inspect, repair or replace. Copy of receipt
of work completed shall be kept to show inspector.
Additional comments: No progress today
GENERATED ON 10/17/25, 8:19 AM 3 OF 8
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Bar electric panel closet
Comments: Cord installation not approved, staff unsure of use of
cord. Repair or replace by licensed electrical contractor.
Additional comments: No progress today
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 2 days past due as of 8/26/25.
Additional comments: Deficiencies per Compliance Engine report
#8039437 states "appliances have been rearranged or added" shall
be corrected.
GENERATED ON 10/17/25, 8:19 AM 4 OF 8
Additional Codes
Status Code
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Electric panel
Comments: Remove obstructions to access electric panels
GENERATED ON 10/17/25, 8:19 AM
5 OF 8
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: Stage area
Comments: Remove power strip plugged to another power strip, shall
be directly plugged to wall outlet. Green cube adapter not approved
for commercial use.
GENERATED ON 10/17/25, 8:19 AM
6 OF 8
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Stage area near back door
Comments: Repeat violation: Remove concealed cord from above
ceiling. Will require to see cord in full removed.
GENERATED ON 10/17/25, 8:19 AM
7 OF 8