COMMERCIAL INSPECTION - 814 LAPORTE RD-08/25/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24834
11/14/2025
12/19/2025
2026-00000202
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Dallas Fresh - 814 La Porte RD, BLDG 814 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
08125/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
SUMMARY OF INSPECTION
® 40
Passed codes
NEXT STEPS
0 23
Failed codes
23
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad-baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/26/2025 0 07:28
$80 annual inspection fee
BRAD BALDWIN - 08/2612025 @ 08:02
Fire extinguishers due annually serviced by January 2026
Shift
NIA
Station
NIA
425 E. 3rd Street
Inspection Number
11796
BRAD BALDWIN - 08/26/2025 @ 10:04
Specific questions regarding electrical requirements shall be directed to Electrical Inspector, Tim Moyer at 319-464-5683.
BRAD BALDWIN - 08/2612025 @ 10:06
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 08/26/2025 @ 10:06
Unit
NIA
Reinspection Date
09/22/2025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 08/26/2025 @ 10:06
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections 8 re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
are
ALBERTO BALTIERRA Date: BRAD BALDWIN 08/2.6/2025
GENERATED ON 8/26/25, 10'16 AM 1 OF 15
CHECKLISTS
Fire Service Features
Status
Fail
0
Cady
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
ptlof
Location: Kitchen suppression system pull handle
Comments: Remove equipment obstructing access to suppression
system pull handle, maintain clear path.
GENERATED ON 8/26/25, 10:16 AM
2 OF 15
Additional Codes
stasis Code
Fail
Fail
601.2 - Hazard abatement.
Operations or conditions deemed unsafe or hazardous by the
fire code official shall be abated. Equipment, appliances,
materials and systems that are modified or damaged and
constitute an electrical shock or fire hazard shall not be used.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Location: Walk in fridge
Comments: Cord unprotected from sharp metal edge should be
corrected to avoid shock hazard. Appliance cord and or plug end
altered, licensed electrical contractor shall inspect, repair or replace.
Copy of receipt of work completed shall be kept to show inspector.
Location: Food warmer near front entrance
Comments: Appliance cord and or plug end altered, licensed
electrical contractor shall inspect, repair or replace. Copy of receipt
of work completed shall be kept to show inspector.
Location: Hallway to mechanical room light fixtures
Comments: Light fixture wiring shall be inspected by licensed
electrical contractor, repaired or replaced . Copy of receipt of work
completed shall be kept to show inspector.
Location: Beverage fridge in front of bar
Comments: Appliance cord and or plug end altered, licensed
electrical contractor shall inspect, repair or replace. Copy of receipt
of work completed shall be kept to show inspector.
GENERATED ON 8/26/25, 10:16 AM
3 OF 15
Fail
606.2 - Where required.
A Type 1 hood shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used
for commercial purposes that produce grease vapors.
Exceptions: 1.Factory-built commercial exhaust hoods that
are listed and labeled in accordance with UL 710, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 71013, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code. Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code. For the
purpose of determining the floor area required to be
ventilated, each individual appliance shall be considered as
occupying not less than 100 square feet (9.3 m2). 3.Where
cooking appliances are equipped with integral down -draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96, a hood shall not be required at or above them. 4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mglm3
or Tess of grease when tested at an exhaust flow rate of 500
cfm (0.236 m3/s) in accordance with UL 71013.
Location: Kitchen exhaust hood and appliances
Comments: Relocate cooking equipment producing grease laden
vapors to be within 6 inches inside of outer edges of hood exhaust
system. Grill top on left side being used as "table" may stay in place
if disconnected from gas service.
GENERATED ON 8/26/25, 10:16 AM
4 OF 15
Electrical Safety
State; Code
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Above table dining area
Comments: Concealed connection above ceiling tiles not approved,
repair or replace by licensed electrical contractor with obtaining
permit and inspection.
GENERATED ON 8/26/25, 10:16 AM 5 OF 15
Fail
Fail
0
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Bar electric panel closet
Comments: Cord installation not approved, staff unsure of use of
cord. Repair or replace by licensed electrical contractor.
Location: Mechanical room light switch
Comments: Install missing switch cover
GENERATED ON 8/26/25, 10:16 AM
6 OF 15
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Ceiling outlet above table dining area
Comments: Install missing outlet cover.
GENERATED ON 8/26/25, 10:16 AM
7 OF 15
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Location: Mechanical room electric panel
Comments: Remove shelf and cart obstructing access to panels,
maintain 36" clearance in front of panel and clear access at all times.
Location: Electric panel closet near bar
Comments: Install permanent sign on door reading "Electrical
Room", red sign with white lettering. Laminated paper will not be
accepted.
GENERATED ON 8/26/25, 10:16 AM
8 OF 15
Fail
O
Fail
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Behind front counter
Comments: Green multi -plug cord shall be removed. Power strip with
manual reset shall be plugged directly to wall outlet used for light
duty electric.
Location: Bar behind cash register
Comments: Remove multi -plug adapters. May replace with properly
mounted or supported power strip with manual reset for light duty
electric. Adding outlet requires licensed electrical contractor to
obtain permit and inspection.
GENERATED ON 8/26/25, 10:16 AM
9 OF 15
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Above front entrance
Comments: Remove brown extension cord hanging through ceiling
tiles. Extension cords not permitted for permanent use, additional
outlets installed as needed will require a licensed electrical
contractor to obtain permits and inspections.
Location: Produce cooler
Comments: Relocate cooler cord running across walkway to avoid
trip hazard and possible damage, or provide UL listed floor cord
protector, or provide electric service from above by licensed
electrical contractor by obtaining permits and inspections.
GENERATED ON 8/26/25, 10:16 AM
10 OF 15
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind front counter
Comments: Remove green extension cord running across walkway.
Additional outlets installed requires licensed electrical contractor to
obtain permits and inspections.
GENERATED ON 8/26/25, 10:16 AM 11 OF 15
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Mechanical room chest freezer
Comments: Remove green extension cord plugged to freezer. Freezer
shall be plugged directly to wall outlet.
Location: Near back entrance and stage
Comments: Remove yellow extension cord hanging through ceiling
tiles. Extension cords not permitted for permanent use, additional
outlets installed as needed will require a licensed electrical
contractor to obtain permits and inspections.
GENERATED ON 8/26/25, 10:16 AM
12 OF 15
Commercial Cooking Hood Suppression System
Stu; Coale
Fail
Fail
Fail
606.3.3.1 - Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.1 - Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSI/IKECA C10.
Location: Kitchen hood exhaust cleaning
Comments: Provide hood cleaning and inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 2 days past due as of 8/26/25.
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 2 days past due as of 8/26/25.
Location: Kitchen hood exhaust filters
Comments: Clean grease filters, currently has build up of
accumulation.
GENERATED ON 8/26/25, 10:16 AM
13 OF 15
Fire Resistant Construction Maintenance
Status
Fail
0
Code
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Mechanical room
Comments: Replace missing ceiling tiles above water heater and
door to mechanical room.
GENERATED ON 8/26/25, 10:16 AM
14 OF 15
Statement of Fees
FEE
Invoice Date rwr,lion Fee
NIA $80.00
Invoice Number
NIA
Date Paid Amount Paid
Check Number Transaction Number
NIA NIA
GENERATED ON 8/26/25, 10:16 AM