HomeMy WebLinkAbout304 W 5TH STINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
11/14/2025
12/19/2025
2026-00000210
$80.00
Customer #: 24830
GOOD GAME
307 W 5TH ST
WATERLOO, IA 50702
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 307 W 5TH ST-09/09/2025
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24830
11/14/2025
12/19/2025
2026-00000210
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Imo' U
Waterloo Fire Rescue
Inspection Report
Good Game - 307 W 5th ST, BLDG 307 W 5th St, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
09/09/2025
Lead Inspector
BRAD BALDWIN
Inspection I v}ie
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
17629
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
e 40
Passed codes
NEXT STEPS
0 13
Failed codes
28
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/09/2025 @ 15:15
$80 annual inspection fee
BRAD BALDWIN - 09109/2025 @ 15:50
Corrected during 9/9/25 inspection: (1) Removed white multi -plug cord in bar area near sink.
BRAD BALDWIN - 09/10/2025 @ 07:19
Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/08/2025
BRAD BALDWIN - 09/10/2025 @ 07:19
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
IRZ
Bud Jones Date: BRAD BALDWIN 0911012025
CHECKLISTS
GENERATED ON 9/10/25. 7 23 AM 1 OF 8
Emergency Equipment
Status Code
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Descripf ion
Location: South exterior egress lights
Comments: Repair or replace light that failed to illuminate during
test.
GENERATED ON 9/10/25, 7:23 AM 2 OF 8
Electrical Safety
Status Code
Fail
Fail
Fait
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Location: Exterior egress light above front entrance
Comments: Repair or replace light to avoid water infiltration inside
fixture.
Location: Back storage
Comments: Relocate small fridge with cord running through doorway
to electric panel room or provide new outlet by licensed electrical
contractor with permit and inspection. Fridge shall plug directly to
wall outlet.
Location: Bar (south end)
Comments: Wiring serving light fixture shall properly enter box
through knockout hole.
GENERATED ON 9/10/25, 7:23 AM 3 OF 8
Fail
x
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Above north wall display cabinet
Comments: Licensed electrical contractor shall repair wire splice not
to code with obtaining permit and inspection.
Location: Above south wall display cabinet.
Comments: Licensed electrical contractor shall repair wire splice not
to code with obtaining permit and inspection.
Location: Electric panel room
Comments: Remove cube multi -plug adapter. Power strip shall plug
directly to wall outlet.
GENERATED ON 9/10/25, 7:23 AM 4 OF 8
Fail
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind juxebox
Comments: Power strip shall be properly supported or mounted to
wall surface to avoid hanging by wires.
Location: Bar area
Comments: Remove multi -plug cord. May replace with properly
mounted or supported power strip with manual reset plugged to wall
outlet.
GENERATED ON 9/10/25, 7:23 AM
5 OF 8
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Additional Codes
Status
Fail
0
Code
807.3 - Acceptance criteria and reports.
Where required to exhibit improved fire performance,
curtains, draperies, fabric hangings and other similar
combustible decorative materials suspended from walls or
ceilings shall be tested by an approved agency and meet the
flame propagation performance criteria of Test Method 1 or
Test Method 2, as appropriate, of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289, using the 20 kW ignition source.
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
Location: Above north wall
Comments: Remove white multi -plug cord. Extension cords allowed
for temporary use only, may replace with properly mounted power
strip with manual reset plugged to wall outlet for light duty electric
only.
Location: East glass display cases
Comments: Remove white multi -plug extension cord. Extension
cords allowed for temporary use only, may replace with properly
mounted power strip with manual reset plugged to wall outlet for light
duty electric only.
Description
Location: Back storage curtains
Comments: Provide
GENERATED ON 9/10/25, 7:23 AM
6 OF 8
Portable Fire Extingusihers
Status Code
Fail
lei
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to fire extinguisher. Most current
service recorded 2022.